Chimney requirements, Ovalizing round stainless steel liners, Chimney top view – Hearth and Home Technologies 3100-I User Manual

Page 8

Advertising
background image

3100-I ACT WOOD INSERT

Page 8

September 1, 2008

R

250-6381D

Floor

Ceiling

Caulk

Floor

(second Story)

Non-Combustible

Firestopping

Material

Minimum 1 inch (25mm)

clearance from exterior

chimney to sheathing

Firestopping

 inch

(51mm)

A chimney must be the required height above the roof
or other obstruction for safety and for proper draft oper-
ation. The requirement is that the chimney must be at
least 3 feet (91cm) higher than the highest point where
it passes through the roof, and at least 2 feet (61cm)
higher than the highest part of the roof or structure that
is within10 feet (305cm) of the chimney, measured hori-
zontally.

Refer to Figure 8C.

CHIMNEY REqUIREMENTS

Non-combustible

fire stopping material

Minimum 2 inch (51mm) clearance

from combustible material

and insulation

ceiling

At least  ft

(61cm)

At least 3 ft

(91cm)

CHIMNEY HEIGHT

10 ft

(305cm)

CHIMNEY TOP VIEW

FLUE

Foundation

1/2" (12.7mm) airspace

5/8" (16mm)

Fireclay Flue

Liner

Chimney Wall

4" (102mm)

Nominal

Figure 8A

Figure 8C

Figure 8B

Figure 8D

OVALIZING ROUND STAINLESS STEEL

LINERS

Ovalizing round stainless steel liners to acommodate

the liner passing through the damper region of a fire-

place is an allowable and acceptable practice.
Ensure that the ovalization is minimized to the extent

required to fit through the damper.