8

Industrial Automation and Control

Honeywell Inc.
http://www.iac.honeywell.com

U.S.A.: Honeywell Industrial Automation and Control, 16404 North Black Canyon Hwy., Phoenix, AZ 85053
Canada: The Honeywell Centre, 155 Gordon Baker Rd., North York, Ontario M2H 3N7
Latin America: Honeywell Inc., 480 Sawgrass Corporate Parkway, Suite 200, Sunrise, Florida 33325
Japan: Industrial Operations Tokyo, 4-28-1 Nishi-Rokugo Ohtu-ku, Tokyo 144, Japan
Asia: Honeywell Asia Pacific Inc., Room 3213-3225, Sun Hung Kai Centre, No. 30 Harbour Road, Wanchai, Hong Kong
Pacific Division: Honeywell Pty Ltd., 5 Thomas Holt Drive, North Ryde NSW Australia 2113
Northern Europe and Southern Africa: Honeywell Ltd., Honeywell House, Arlington Business Park, Bracknell, RG 12 1EB, U.K.
Central Europe: Honeywell A.G., Kaiserleistraße 39, 63067 Offenbach, Germany
Western and Southern Europe: Honeywell S.A., Avenue de Schiphol 3, 1140 Brussels, Belgium
Eastern Europe: Honeywell Praha, s.r.o., Budejovicka 1, 140 00 Prague 4, Czech Republic
Middle East: Honeywell Middle East Ltd., Khalifa Street, Sheikh Faisal Building, Abu Dhabi, U.A.E.

© Honeywell Inc. Printed in U.S.A.

Recycled Paper

4 Analog Inputs

– 1 to 5 Vdc, 4-20mA or 10 to 50 mA
– Isolated from all other inputs and outputs

Universal Input — isolated

– Thermocouple

– Millivolts or Volts

– RTD

– Pulse

1 or 2 Current Outputs

– 4-20mA dc
– Isolated

4 Universal Digital Inputs /Outputs

– Open-collector outputs or digital inputs
– Externally powered

2 Digital Inputs

– User configurable
– Isolated

Math Functions

– summer

– input/output

– weighted average

characterization

– multiplier/divider

– logic

– hi/lo select

– totalization

Serial Communications Link

– RS485 TDC 3000 Integration

– DMCS

– RS422/485 — 15 drops

Transmitter Power

– 24Vdc

±

2V

– 50mA dc for one or two transmitters

Accuracy

– ±0.01% of span for linear inputs
– ±0.02% of span typical for T/C and RTD inputs

Temperature Stability

– ±0.005% per F° typical

Pulse Input

– Range: 1Hz to 25K Hz

Power Consumption

– 20 VA maximum

Splashproof faceplate

Power Requirements

– 24Vdc, 120 Vac or 240 Vac

CE Mark Compliant

– Full conformity with CE directives

51-51-58-18 (7.5M) 10/98

Condensed Specifications (some features are optional)

For complete product specifications please request

document 51-52-03-13.

Specifications are subject to change without notice.

™ACCUTUNE is a U.S. trademark of Honeywell, Inc.

*All other brand and product names are trademarks of their respective owners.

144

5.67

72

2.83

138

5.43

+1.0

-0

+0.039

-0

+0.7

-0

+0.027

-0

68

2.68

panel cutout

(DIN

Standard)

Dimensions:

millimeters

inches

233

9.19
max

33

1.22
max

25

1.00

Max. Panel
thickness

NOTES:

1. Drawing is not to scale
2. No minimum horizontal

spacing is defined.

3. Controller may be

mounted at any angle
or tilt.

Rear Terminal Cover