Air remov al, Connection of power cord, Outdoor unit final st age of inst alla tion – Hitachi RAS-35YH6 User Manual

Page 2

Advertising
background image

• Please mount the Outdoor unit of stable ground to prevent vibration and increase

of noise level.

• Decide the location for piping after sorting out the different types of pipe available.
• When removing side cover, please pull the handle after undoing the hook by pulling

it downward. Reinstall the side cover in the reverse order of the removal.

Pull downward

Please face this side (suction side)
of the unit to the wall.

Please remove side cover
when connecting the piping
and connecting cord.

CONDENSED WATER DISPOSAL OF OUTDOOR UNIT

• There is holes on the base of Outdoor unit for condensed water to exhaust.
• In order to flow condensed water to the drain, the unit is installed on a stand or a

block so that the unit is 100mm above the ground as shown figure. Join the drain
pipe to one hole.

• Cover the drain hole with a bush. To install the bush, put it on the drain hole as

shown in the figure and press the both sides of the bush to fit into the hole.
After installation, check whether the drain pipe and bush cling to the base firmly.

• Install the outdoor unit horizontally and make sure that condensate drains away.
• In case of using in chilly area

Especially, in case that there are many snows by very cold in chilly area, condensed
water freezes on the base and may result not to drain. In this case, please remove
the bush and the drain pipe at the bottom of unit. (Left and center near discharge
portion of air, each 1 place). It becomes smooth drain.
Ensure that the distance from the drain hole to the ground is 250 mm or more.

0 DRAIN PIPE

9 BUSH

DRAIN HOLE

above
100mm

CAUTION

• Remove burr and jagged edge will cause leakage.
• Point the side to be trimmed downwards during trimming to prevent copper

chips from entering the pipe.

Copper pipe

Trimming tool

• Before flaring, please put on the flare nut.

A

Die

Die

Copper pipe

• Please use

exclusive tool for
refrigerant R410.

Outer A (mm) Rigid Flaring Tool

Diameter (Ø)

For R410A tool

For R22 tool

6.35 (1/4")

0 - 0.5

1.0

9.52 (3/8")

0 - 0.5

1.0

2

Pipe Connection

CAUTION

• In case of removing flare nut of a indoor unit, first remove

a nut of small diameter side, or a seal cap of big diameter
side will fly out. Free from water into the piping when
working.

• Be sure to tighten the flare nut to the specified torque with

a torque wrench.
If the flare nut is overtightened, the nut may be split after a
long period has passed, and may cause a refrigerant leak.

• Please be careful when bending the copper pipe.
• Screw in manually while adjusting the center. After that, use a torque wrench to

tighten the connection.

INST

ALLA

TION OF REFRIGERA

TING PIPES

AND

AIR REMOV

AL

Torque
wrench

Flare nut

Wrench

Small diameter side

6.35 (1/4")

13.7 – 18.6 (140 – 190)

Large diameter side

9.52 (3/8")

34.3 – 44.1 (350 – 450)

Small diameter side

6.35 (1/4")

19.6 – 24.5 (200 – 250)

Large diameter side 9.52 (3/8")

19.6 – 24.5 (200 – 250)

Valve core cap

12.3– 15.7 (125 – 160)

Outer diameter

of pipe (ø)

Torque N·m

(kgf·cm)

Valve

head cap

3

Remove of Air From The Pipe And Gas Leakage Inspection

AIR REMOV

AL

Procedures of using Vacuum Pump for Air Removal

As shown in right figure, remove the cap
of valve core. Then, connect the charge
hose. Remove the cap of valve head.
Connect the vacuum pump adapter to the
vacuum pump and connect the charge
hose to the adapter.

1

Fully tighter the "Hi" shuttle of the manifold
valve and completely unscrew the "Lo"
shuttle. Run the vacuum pump for about
10-15 minutes, then completely tighten the
"Lo" shuttle and switch off the vacuum
pump.
• Loosen the spindle of the service valve

with small diameter by 1/4 turn and
tighten the spindle immediately after 5
to 6 seconds.

• Remove the charging hose from the

service valve.

2

Completely unscrew the spindle of the
service valve (at 2 places) in anticlockwise
direction to allow the flow of refrigerant
(using Hexagonal Wrench key).

3

Tighten the cap of valve head. Check the
cap's periphery if there is any gas leakage.
The task is then completed.

4

When the meter reaches - 101KPa
(-76cmHg) during pumping fully
tighten the shuttle.

Meter showing
pressure

Closed

R410A
Manifold
valve

Vacuum
pump

Valve

Charge
hose

Vacuum
pump
adapter

When pumping starts, slightly
loosen the flare nut to check of
air sucked in. Then tighten the
flare nut.

The body of service
valve

Cap of
valve core

Hexagonal
wrench Key

Cap of valve
head

Gas leakage inspection

Please use gas leakage detector to check if leakage
occurs at connection of Flare nut as shown on the
right.

If gas leakage occurs, further tighten the connection
to stop leakage.

CONNECTION OF POWER CORD

When power supplies to Indoor Unit

WARNING

• The naked part of the wire core should be 10mm fix it to the terminal tightly. Then

try to pull the individual wire to check if the contact is tight. Improper insertion may
burn the terminal.

• Be sure to use only wire specified for the use of air-conditioner.
• Please refer to the manual for wire connection and the wiring technique should

meet the standard of the electrical installation.

• There is an AC voltage drop between the LN terminal if the power is on. Therefore,

be sure to remove the plug from its socket.

OUTDOOR UNIT

FINAL

ST

AGE OF INST

ALLA

TION

1

Preparation of Pipe

• Use a pipe cutter to cut the copper pipe and remove burr.

1

Power Source And Operation Test

2

Installation of Remote Controller

• The remote controller can be placed in its holder which is fixed

on wall or beam.

• To operate the remote controller at its holder, please ensure that

the unit can receive signal transmitted from the controller at the
place where the holder is to be fixed. The unit will beep when
signal is received from the remote controller. The signal
transmission is weaken by the fluorescent light. Therefore, during
the installation of the remote control holder, please switch on
the light, even during day time, to determine the mounting location
of the holder.

The controller must be hooked onto the hook at the lower part
of the holder. Push in the remote controller in the direction as
shown in figure below.

Power Source

WARNING

• Never remodel the power plug nor extend the long-distance

cord.

• Keep additional length for the power cord and do not render

the plug under external force as this may cause poor contact.

• Do not fix the power cord with U-shape nail.
• The power cable easily generates heat. Do not bring the

cable together with a wire or vinyl tie.

Operation test

• Please ensure that the air conditioner is in normal operating

condition during the operation test.

• Explain to your customer the proper operation procedures as

described in the user' s manual.

• If the indoor unit won't operate, check the cable for correct

connection.

• Turn on the lamp in the room where the indoor unit is installed

and check the remote controller for normal operation.

How to remove the front cover

How to Attach the Front Cover

¡

Check that the drain pan is securely attached.

After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
the front cover to lock the claws.

£

Tighten the two screws.

¢

Install the filter.

Slide the shafts of the right and left arms on the front panel
along the steps to insert the shafts into the holes till they stop.
After checking that the shafts are securely inserted, close the
panel.

¡

Remove the front panel

• Please remove and attach the front panel by both hands.

• After opening the front panel by both hands.

1

Undo the right arm while pushing it inside.

2

Slide the front panel to right as shown in figure. Then remove
while pulling it to front.

Remove the filters.

£

After removing two screws, pull the center of the front cover
towards you and release the claws.

¢

Pull the side faces (lower sections) of the front cover towards
you as shown in the figure and remove the cover.

WARNING

• THIS APPLIANCE MUST BE

EARTHED.

Procedures of Wiring

Cap of valve
head

Remote controller

Screw (2 pieces)

Holder for Remote
Controller

< S735 : A >

Valve

Step

Shaft

Hole

CAUTION

• Do not touch the suction

port, bottom surface, or
aluminum fin of the outdoor
unit.
Failure to do so may cause
an injury.

Push

Push

BASE

DRAIN HOLE

9 BUSH

Outer diameter: 16 mm or more

WARNING

• Leave some space in the connecting cord for maintenance

purpose and be sure to secure it with the cord band.

• Secure the connecting cord along the coated part of the wire

using the cord band. Do not exert pressure on the wire as this
may cause overheating or fire.

30mm

10mm

70mm

30mm

10mm

30mm

10mm

30mm

10mm

10mm

Line cord

Indoor Unit

Outdoor Unit

ø2.0

Connecting Cord

ø1.6 or ø2.0

Detail of cutting the connecting cord

Green + Yellow

Green + Yellow

Indoor Unit

Outdoor Unit

Strip wires

Strip wires

When power supplies to Outdoor Unit

Detail of cutting the connecting cord

ø1.6 or

ø2.0

Indoor Unit

Outdoor Unit

Connecting Cord

30mm

10mm

10mm

70mm

10mm

50mm

10mm

50mm

Green + Yellow

Green + Yellow

Green + Yellow

Strip wires

Indoor Unit

Outdoor Unit

Wiring of The Indoor Unit

• For wire connection of the Indoor unit, you need to remove the front cover, the low cover

under the body of the unit and terminal cover.

• Power cannot be turned off using power switch.

Always keep the switch "off" and put the switch cover
on the power switch so that the power cannot be turned
on.

• Power cord is not necessary, store it in the lower-side space on the rear

side of indoor unit. When storing, warp the power plug with the vinyl bag
for the parts, etc. and seal with adhesive tape to prevent dust or dirt.

• Terminal A and B of indoor unit do not need to be connected.
• When power supplied to outdoor unit, power is not turned off by switching

the power of indoor unit to "off". In that case, please cut the breaker.

When power supplied to outdoor unit

• Remove the cover from the terminal base and screw the cable.

D
C
B
A

After remove the screw
and terminal cover, and
put the connecting cords
and fix the terminal cover
with screw.

Earth

Screw

Insulating plate

Cord band

Connecting cord

Securely screw in the power cord and
connecting cord so that it will not get loose
or disconnect.
Tightening torque reference value:
1.2 to 1.6 N·m (12 to 16 kgf·cm)
Excessive tightening may damage the
interior of the cord requiring replacement.

When putting two connecting cords
through the band.

Terminal cover

• Wiring for the horizontal piping from the right side.

Not to interfere with the drain hose, fold the cable at the
drain hose side of the electric box as shown in the left
figure, and pass the cable just over the electric box and
pull it out.

Cable

Pipe

Drain

Power cord

• Pull at the ¡ and ™ in the directions as shown by

arrows to remove the cover.

Method to remove the low cover

WARNING

If you cannot attach the side plate due to the connection cord, please
press the connecting cord in the direction to the front panel to fix it.

Be sure that the hooks of the side cover fixed in certainly. Otherwise water
leakage may occur and this causes short circuit or faults.

The connecting cord should not touch to service valve and pipes. (it
becomes high temperature in heating operation.)

Wiring of the Outdoor Unit

• Please remove the side cover for wire connection.

Checking for the electric source and the voltage range

• Before installation, the power source must be checked and necessary wiring work must

be completed. To make the wiring capacity proper, use the wire gauge list below for the
wiring from house distribution fuse box to the outdoor unit in consideration of the blocked
rotor current.

IMPORTANT

Wire length

Wire gauge

up to 6m

1.6mm

2

up to 15m

2.5mm

2

up to 20m

4.0mm

2

• Investigate the power supply capacity and other

electrical conditions at the installing location.
Depending on the model of room air conditioner to be
installed, request the customer to make arrangements
for the necessary electrical work etc.
The electrical work includes the wiring work up the
outdoor unit. In localities where electrical conditions
are poor, use of a voltage regulation is recommended.

• Install outdoor for the room air conditioner within the

reaching range of the line cord.

cover

Earth terminal

IMPORTANT

Fuse Capacity

16A time delay fuse

Force-cooling operation

• When the service switch

of the indoor unit is
pressed for 1 or more
seconds, the force-
cooling operation starts.
Use this mode when
performing the failure
diagnosis or collecting
refrigerant into the
outdoor unit.

CAUTION

• Do not operate the unit for more than 5 minutes

while the spindle of the service valve is closed.

• Push up the [PUSH] sections at the bottom of the indoor unit and

pull the bottom plate towards you. Then the claws are released
from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)

HOW TO REMOVE INDOOR UNIT

[PUSH] mark positions

Connecting cord

Connecting cord

Electric box

After completing the service switch
operation, be sure to keep the
switch pressed for one or more
seconds and stop the force-cooling
operation.

Service switch (If the switch is
pressed for one or more seconds, the
force-cooling operation starts. If the
switch is pressed for additional one or
more seconds, the operation stops.)

Screw

Cover

Cable

Power
cord

Pipe

Drain
hose

Screw

Form the cable properly so that the
low cover won’ t touch the cable in
installation.

Piping and drain hose layout

WARNING

After wiring the indoor unit, make sure
to reattach the terminal cover.

06K108_RAS-35_YH6_English.p65

11/9/06, 10:58 AM

2

Advertising
This manual is related to the following products: