PROGRAMMING

GLOBAL OPTIONS

ANCILLARY TRIP

1

LATCHING

NORMALLY DE-ENERGISED

2

NON-LATCHING

NORMALLY DE-ENERGISED

3

LATCHING

NORMALLY ENERGISED

4

NON-LATCHING

NORMALLY ENERGISED

ALARM VERIFICATION

1

DISABLED

2

2 MINUTES

3

3 MINUTES

4

4 MINUTES

5

5 MINUTES

TIME

(DD) / (MM) / (YY)

(HH) : (MM)

ZONE OPTIONS

DESCRIPTION

INPUT DELAY

1

Standard Latching

2 seconds

2

Standard Latching

2 seconds with AVF

3

Non Latching

2 seconds

4

Non Latching

20 seconds

5

Time Delay

10 seconds

6

Time Delay

20 seconds

7

Time Delay

30 seconds

8

Time Delay

40 seconds

9

Time Delay

50 seconds

10

Time Delay

60 seconds

Type

Output Description

1

Indicate Only

2

Indicate, Bell

3

Indicate, Bell, General Alarm

4

Indicate, Bell, General Alarm, Ancillary

5

Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1

6

Indicate, Bell, General Alarm, Ancillary Brigade Relay #2

7

Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2