Termination locations, Warning, A. vent termination minimum clearances – Heat & Glo Fireplace Heat & Glo 550TRSI-AUF User Manual

Page 24

Advertising
background image

Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF • 2079-980 Rev. R • 2/13

24

A. Vent Termination Minimum Clearances

Figure 6.1 Minimum Height From Roof To Lowest Discharge

Opening

6

Termination Locations

Fire Risk.
Maintain vent clearance to combustibles as

specified.

DO NOT pack air space with insulation or other

materials.

Failure to keep insulation or other materials away

from vent pipe may cause overheating and fire.

WARNING

H (MIN.) - MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

VERTICAL

WALL

TERMINATION

CAP

HORIZONTAL

OVERHANG

305 mm

X

ROOF PITCH

IS X/ 305 mm

LOWEST

DISCHARGE

OPENING

510 mm MIN.

610 mm MIN.

Angle

H (Min.) mm

0°-26.6° .......................................................... 500*
26.6°-30.3° .......................................................... 500*
30.3°-33.7° .......................................................... 500*
33.7°-36.9° .......................................................... 610*
36.9°-39.8° .......................................................... 760
39.8°-42.5° .......................................................... 990
42.5°-45.0° ........................................................1 220
45.0°-49.4° ........................................................1 520
49.4°-53.1° ........................................................1 830
53.1°-56.3° ........................................................2 130
56.3°-59.0° ........................................................2 290
59.0°-60.3° ........................................................2 440

*910 mm minimum in snow regions

Figure 6.2 Staggered Termination Caps

Gas, Wood or Fuel Oil

Termination Cap

B

Gas

Termination

Cap **

A *

*

If using decorative cap cover(s), this distance may need to be

increased. Refer to the installation instructions supplied with the

decorative cap cover.

**

In a staggered installation with both gas and wood or fuel oil

terminations, the wood or fuel oil termination cap must be

higher than the gas termination cap.

A

B

6 in. mm (min.) up to 20 in.

(152 mm (min.) up to 508 mm)

18 in. minimum

(457 mm minimum)

20 in. minimum

(508 mm minimum)

0 in. minimum

(0 mm minimum)