Hubbell LightHawk LHUS User Manual

Installation and operating instructions, Lighthawk, Wall switch occupancy sensors

Advertising
background image

Description
Th

e LightHAWK is an intelligent self-adapting occupancy sensor that is

designed to replace existing wall switches.

Specifi cations

• 1000 sq. ft coverage area (Models: LHIR and LHMT)

• 400 sq. ft. coverage area (Models: LHUS)

• Single or Dual circuit 120/277VAC, 50/60Hz operation

• Electrical Ratings: (Each Output Separately)

120VAC – 800W Incandescent, 1000W Ballast, 1/6 HP

277VAC – 1800W Ballast, 1/6 HP

• Adjustable Time Delay: 4-30 minutes, self-adapts based

on

occupancy

• Light Level Adjustment (Circuit B output on Dual Circuit versions):

10-500+FC

• ETL listed (Conforms to UL STD 508 Certifi ed to CAN/CSA STD

C22.2 No. 14)

Precautions
CAUTION: RISK OF ELECTRICAL SHOCK. Turn power off at
service panel before beginning installation. Never wire energized electrical
components.

Read and understand all instructions before beginning installation.

NOTICE: For installation by a licensed electrician in accordance with
National and/or local Electrical Codes and the following instructions.

NOTICE: For indoor use only.

CAUTION: USE COPPER CONDUCTOR ONLY.

Confi rm that device ratings are suitable for application prior to installation.

NOTICE: Do not install if any damage to product is noticed.

Installation
1. Turn power off at the service panel.
2. Remove the old switch(es) if applicable.
3. Wire as shown in the Wiring Diagram section. A secure connection

to ground is necessary for the sensor to function properly.

4. Install sensor in wall box using mounting screws provided.
5. Restore power to the sensor and allow it to warm up (up to 2 min.).
6. Remove the sensor’s cover – see Adjustments section.
7. If desired, calibrate the photocell sensor and adjust the sensor’s
confi guration switch settings as described below.
8. Reinstall the sensor’s cover.
9. Install a Decorator style wall plate (not included).

Test Mode – to enter test mode:
1. Make sure lights are on.

LightHawk

Wall Switch Occupancy Sensors

Installation and Operating Instructions

Hubbell Building Automation, Inc.
9601 Dessau Road, Building One, Suite 100
Austin, Texas 78754
512-450-1100 • 512-450-1215 Fax
www.hubbell-automation.com

Wiring Diagram

Sensor Operation

Range Diagram

Advertising
This manual is related to the following products: