CHECKOUT

Allow the C7189 Wall Mount Temperature Sensor to soak
in the air moving through the room for a minimum of five
minutes before taking a resistance measurement.

With an accurate thermometer (

±

1

°

F [0.5

°

C]), measure the

temperature at the sensor location, allowing time for the
thermometer to stabilize before reading. Remove one wire
from one of the C7189 wiring terminals. Use an ohmmeter
to measure the resistance across the sensor. Then verify
sensor accuracy with the temperature/resistance curve of
Fig. 3.

CALIBRATION

The C7189 Remote Sensor is calibrated at the factory and
cannot be recalibrated in the field.

Home and Building Control
Honeywell Inc.
1985 Douglas Drive
Golden Valley, MN 55422

Fig. 3. C7189 Sensor Resistance vs. Temperature Performance Characteristics.

OHM RESISTANCE

°F
(°C )

M6357

RESISTANCE DECREASES 18.6 OHMS PER 1°F
CHANGE OR 33.4 OHMS PER 1°C CHANGE.

1

1

2000

2100

1900

1500

1600

1700

1800

1400

TEMPERATURE

40

(4)

50

(10)

60

(16)

70

(21)

80

(27)

90

(32)

100

(38)

1300

1000

1200

2200

2300

46

48

50

52

54

56

58

60

62

64

66

68

70

72

74

76

78

80

82

84

86

88

90

92

94

96

98

100

7.8

8.9

10.0

11.1

12.2

13.3

14.4

15.6

16.7

17.8

18.9

20.0

21.1

22.2

23.3

24.4

25.6

26.7

27.8

28.9

30.0

31.1

32.2

33.3

34.4

35.6

36.7

37.8

2131 to 2094

2094 to 2057

2057 to 2019

2019 to 1982

1982 to 1945

1945 to 1908

1908 to 1871

1871 to 1833

1833 to 1796

1796 to 1759

1759 to 1722

1722 to 1685

1685 to 1647

1647 to 1610

1610 to 1573

1573 to 1536

1536 to 1499

1499 to 1461

1461 to 1424

1424 to 1387

1387 to 1350

1350 to 1313

1313 to 1275

1275 to 1238

1238 to 1201

1201 to 1164

1164 to 1127

1127 to 1089

ROOM TEMPERATURE

OHMS OF

RESISTANCE

°F

°C