Installation and operations manual, Table 2. pressure loss of liquid refrigerants, Table 3. equivalent feet of pipe – Heatcraft Refrigeration Products PARALLEL COMPRESSOR SYSTEMS 25000102 User Manual

Page 10

Advertising
background image

10

Part # 25000102

Installation and Operations Manual

Liquid Line Rise in Feet

Refrigerant

10’

15’

20’

25’

30’

40’

50’

75’

100’

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

R-12

5.4

2.8

8.1

4.2

10.7

5.4

13.4

6.9

16.1

8.3

21.5 11.3 26.9 14.3 40.3 22.4 53.7 31.0

R-22

4.8

1.6

7.3

2.3

9.7

3.1

12.1

3.8

14.5

4.7

19.4

6.2

24.2

8.0

36.3 12.1 48.4 16.5

R-502

4.9

1.5

7.3

2.2

9.7

3.0

12.1

3.7

14.6

4.5

19.5

6.0

24.3

7.6

36.4 11.5 48.6 14.8

R-134A

4.9

2.0

7.4

2.9

9.8

4.1

12.3

5.2

14.7

6.3

19.7

8.8

24.6 11.0 36.8 17.0 49.1 23.7

R-404A/R-507 4.1

1.1

6.1

1.6

8.2

2.1

10.2

2.7

12.2

3.3

16.3

4.1

20.4

5.6

30.6

8.3

40.8 11.8

Table 2. Pressure Loss of Liquid Refrigerants

(In Liquid Line Risers - Expressed in Pressure Drop, PSIG, and Subcooling Loss, °F)

Based on 110°F liquid temperature at bottom of riser

Table 3. Equivalent Feet of Pipe

(Due to Value and Fitting Friction)

Copper Tube

OD, Type “L”

1/2

5/8

7/8

1-1/8 1-3/8 1-5/8 2-1/8 2-5/8 3-1/8 3-5/8 4-1/8 5-1/8 6-1/8

Globe Value (Open)

14

16

22

28

36

42

57

69

83

99

118

138

168

Angle Value (Open)

7

9

12

15

18

21

28

34

42

49

57

70

83

90° Turn Through Tee

3

4

5

6

8

9

12

14

17

20

22

28

34

Tee - Straight Through

or Sweep Below

.75

1

1.5

2

2.5

3

3.5

4

5

6

7

9

11

90° Elbow or Reducing

Tee (Straight Through)

1

2

2

3

4

4

5

7

8

10

12

14

16