Cable routing guidelines, Separation of power and data cables, Retention of excess cable – HP DVP 3040 User Manual

Page 3: Protection of cables, Securing cables and connectors, Securing data cables

Advertising
background image

Cable routing guidelines

To minimize maintenance, safety, and performance issues, routing of power and data cables should

be in accordance with the following guidelines.

Separation of power and data cables

Cables in close proximity to each other, especially those oriented in parallel or in loops, can create

electromagnetic interference (EMI) through induction. EMI can result in erratic or error-prone data
transfers. To minimize the effects of EMI, power cables should be segregated from data cables as

much as possible:

Dress all signal cables on the left side of the rack and all power cables on the right side of the rack.

Arrange and secure excess power and data cabling separately.

Use HP cable management kits described later in this paper to facilitate the segregation.

Retention of excess cable

Installing a number of components in a rack typically results in the use of some cables that are longer

than necessary. This is especially true when similar or redundant components with the same cable

types are installed at various levels in a rack. The excess cable lengths are often hurriedly bundled

and tied, resulting in problems associated with EMI or in damaged cables.
Here are some preferred methods of handling excess cables:

Run and attach excess cables for easy, safe maintenance activities and proper operations.

Ensure that secured cables are not pinched, damaged, or kinked (refer to the “

Cable bend radius

restrictions

” section of this paper).

When possible, use all cable management arms included in component kits.

Use HP cable management kits described later in this paper for maintaining and managing cables.

Protection of cables

Cables must be protected at points where they might rub or come in contact with sharp edges or

heated areas. Extra care must be used with power cables because damaged conductors could cause
downtime and because exposed conductors are a safety hazard.
To protect cables, HP recommends the following practices:

Avoid dressing cables tightly over sharp edges of railing or panels.

Avoid pinching of cables between components or mounting/sliding rails.

Protect the cables if they may be pinched or damaged.

Securing cables and connectors

Cables and connectors should be secured to prevent excessive movement and to provide strain relief

at critical points.

Securing data cables
For securing data cables, HP recommends the following practices:

Ensure that cable connections are not stressed from any cable or chassis movement.

Dress cables on management arms securely enough to prevent interference with movement or

pinched cables, yet not so tight as to cause binding to the arm.

3

Advertising