Symbology – Harbor Freight Tools Chicago 94560 User Manual

Page 7

Advertising
background image

Page 7

For technical questions, please call 1‑800‑444‑3353.

SKU 94560

Make sure the extension cord is properly

7.

wired and in good electrical condition.

Always replace a damaged extension

cord or have it repaired by a qualified

electrician before using it.
Protect the extension cords from sharp

8.

objects, excessive heat, and damp or

wet areas.

reCOMMended MiniMuM wire gauge

FOr eXtensiOn COrds*

(120/240 VOlt)

naMeplate

aMperes

(at full load)

eXtensiOn COrd

length

25’ 50’ 75’ 100’ 150’

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

table a

* based on limiting the line volt‑

age drop to five volts at 150% of

the rated amperes.

symbology

Double Insulated

Canadian Standards Association

Underwriters Laboratories, Inc.

V~

Volts Alternating Current

a

Amperes

spM

Strokes Per Minute

n0 xxxx/min.

No Load Revolutions per Minute

(RPM)

Advertising