Honeywell s HercuLine 2000 User Manual
Page 3
62-86-25-14
Quick Start Guide for Herculine 2000 Series Actuators
February 2007
Page 3 of 10
CW from
Controller
5
CW Motor Drive
CCW from
Controller
6
CCW Motor Drive
Potentiometer #1
7
8
9
Clockwise-End
Slidewire feedback
Counterclockwise-End
Potentiometer #2
10
11
12
Clockwise-End
Slidewire feedback
Counterclockwise-End
Protective Ground
Ground wire connection for main supply
HercuLine
®
2001/2002 Wiring Connections
Auxiliary
Connector
_
Brown
Black
Blue
+
Black Wire Not Used
HART connection using
external Turck connector
+
_
HART
Communications
Connection
Auxiliary
Connector
_
Brown
Black
Blue
+
Black Wire Not Used
HART connection using
external Turck connector
Auxiliary
Connector
_
Brown
Black
Blue
+
Black Wire Not Used
HART connection using
external Turck connector
+
_
HART
Communications
Connection
Figure 3 HercuLine
®
2001/2002 Connections
Connection
Terminal
Description
TB1
Hot
1
Hot wire for 120/240VAC main supply
Neutral
2
Neutral wire for 120/240VAC main supply
Protective Ground
3
Ground wire connection for main supply
Auto/Manual Switch
Contact
4
5
Switch contact to indicate setting of actuator AUTO/MANUAL switch.
Switch is closed when actuator is “NOT-IN-AUTO”
6
TB3
4 to 20mA Output*
1 (+)
2 (-)
Analog signal output
Feedback 3
Feedback signal used in conjunction with 4 to 20mA OUTPUT voltage
when using Slidewire Emulation
4 to 20mA Input
4 (+)
5 (-)
Analog signal input
Modbus
Communication
6 (+)
7 (-)
8 Shield
Connection for RS485 Modbus loop wires
HART
Communications
4 (+)
5 (-)
HART Communication is
4-20 mA only.
Digital Input
9 Com
10 Input
Customer’s contact closure
*
Optional