Honeywell s HercuLine 2000 User Manual

Page 3

Advertising
background image

62-86-25-14

Quick Start Guide for Herculine 2000 Series Actuators

February 2007

Page 3 of 10

CW from
Controller

5

CW Motor Drive

CCW from
Controller

6

CCW Motor Drive

Potentiometer #1

7
8
9

Clockwise-End
Slidewire feedback
Counterclockwise-End

Potentiometer #2

10
11
12

Clockwise-End
Slidewire feedback
Counterclockwise-End

Protective Ground

Ground wire connection for main supply

HercuLine

®

2001/2002 Wiring Connections

Auxiliary

Connector

_

Brown

Black

Blue

+

Black Wire Not Used

HART connection using
external Turck connector

+

_

HART

Communications

Connection

Auxiliary

Connector

_

Brown

Black

Blue

+

Black Wire Not Used

HART connection using
external Turck connector

Auxiliary

Connector

_

Brown

Black

Blue

+

Black Wire Not Used

HART connection using
external Turck connector

+

_

HART

Communications

Connection

Figure 3 HercuLine

®

2001/2002 Connections

Connection

Terminal

Description

TB1

Hot

1

Hot wire for 120/240VAC main supply

Neutral

2

Neutral wire for 120/240VAC main supply

Protective Ground

3

Ground wire connection for main supply

Auto/Manual Switch
Contact

4
5

Switch contact to indicate setting of actuator AUTO/MANUAL switch.
Switch is closed when actuator is “NOT-IN-AUTO”

6

TB3

4 to 20mA Output*

1 (+)
2 (-)

Analog signal output

Feedback 3

Feedback signal used in conjunction with 4 to 20mA OUTPUT voltage
when using Slidewire Emulation

4 to 20mA Input

4 (+)
5 (-)

Analog signal input

Modbus
Communication

6 (+)
7 (-)
8 Shield

Connection for RS485 Modbus loop wires

HART
Communications

4 (+)
5 (-)

HART Communication is
4-20 mA only.

Digital Input

9 Com
10 Input

Customer’s contact closure

*

Optional

Advertising