Caution – Honeywell ML6874 User Manual

Page 5

Advertising
background image

ML6874

WIRING

3

SPDT

Controller

2

ML6874

28 Vdc

OR

+

T6

T5

24 Vac

1

L1

L2

T5

T6

W

R

B

Caution:

In multiple actuators connection, power supply to all
actuators must be connected in a TRUE parallel fashion
to reduce excessive voltage drop. DO NOT "daisy chain"
i.e. connected to one actutator then branched to another.

!

ML6874

2

W

B

R

W

B

R

T5

T6

W

R

B

3

1

2

Allow 0.5 amps maximum for each device. Actuators and controller can share same transformer providing the
VA rating of the transformer is not exceeded and proper phasing is observed.

Use configuration DIP switches to select device functions: Direct acting function (actuator stem moves upwards
with R & B closed ) or Reverse acting function ( actuator stem moves downwards with R & B closed ). DO NOT
reverse wiring.

SPDT controller can be a low voltage Series 20 "on-off " or Series 60 "floating" (center-off) type.

Configuration

FUNCTION

DIP switches
located adjacent

Direct Acting Mode

to the input
terminal block

Reverse Acting Mode

NOTE:

Turn power off before setting the DIP switches.

DIP SWITCH CONFIGURATION

on

off

1

2

3

4

on

off

1

2

3

4

Fig. 7 Wiring for SPDT controller to ML6874 actuators

5