Hubbell Industrial Controls, Inc

Lifting Magnet Power Supplies

Specifications 4320 * January 2000
Replaces February 1994

4320

General

Hubbell offers the Type 4320 diode rectifier,
specifically designed and rated for the demand-
ing requirements where short circuits on the DC
output bus are common or probably. The unit is
ideally suited for applications such as scrap lift-
ing magnets or cranes.

Addressing the common problem of blown semi-
conductor fuses resulting from cut magnet ca-
bles, shorted magnets, or crane rail faults. The
4320 offers a rectifier system that eliminates all
fusing in the rectifier. Traditional rectifier design
incorporates the use of silver and, fast acting,
current limiting, semi-conductor fuses to protect
rectifier diodes in the event of a DC fault. The
4320 rectifier design eliminates the need for
these fuses.

The 4320 rectifier design will trip the unit’s AC
input breaker in the event of a DC output bus
fault. After the fault is cleared, the user simply
resets the unit’s AC breaker and the unit is op-
erational.

Cost Savings:

♦ No blown fuses to replace

♦ No spare fuses to inventory

♦ Downtime associated with changing power

semi-conductor fuses is eliminated

Standard Features of the Type
4320 Rectifier:

♦ AC input voltage: 460V, 3Ph, 60Hz.

♦ Nominal DC output: 240VDC

♦ AC molded case circuit breaker

♦ Dry Type isolation transformer: Transformer

has one 5% tap above and below nominal
input voltage

♦ DC bleed resistor

♦ Full wave, six pulse, diode rectifier assem-

bly; mounted on oversize extruded alumi-
num head sinks

♦ Diode peak inverse voltage to be six times

the bridge AC RMS voltage

♦ Heavy Duty surge suppression specifically

rated for highly inductive load kick applica-
tion. i.e. Magnets

♦ Power on indication light

♦ Industrial duty floor mounted NEMA 2 in-

door, or NEMA 3R outdoor, convection
cooled, vented enclosure with hinged door
access

♦ Single side access to all components

♦ Enclosure grounding lug

Options:

♦ DC ammeter and/or voltmeter

♦ Remote on/off pushbutton

♦ Flange mounted on/off pushbutton

Advertising