Heat & Glo • 6000TRS-CE • 2049-900 Rev. R • 3/13

23

Figure 18. Flue Pipe & Firestop

For vertical Runs - One firestop is REQUIRED at the hole

in each ceiling through which the flue passes.
To install firestops for vertical runs that pass through

ceilings:
• Position a plumb bob directly over the center of the verti-

cal flue component.

• Mark the ceiling to establish the center point of the flue.
• Drill a hole or drive a nail through this center point.
• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the heater and flue system, if necessary, to

accommodate the ceiling joists and/or obstructions.

• Cut a 25.4 cm X 30.5 cm hole through the ceiling, using

the firestop pipe opening as a guide.

• Frame the hole with framing lumber the same size as

the ceiling joists.

Figure 19. Hole and New Framing Members

CEILING

NEW

FRAMING

MEMBERS

EXISTING CEILING

JOISTS

CHIMNEY

HOLE

10" (25.4 cm)

)

m

c

4

.

5

2

(

0

1

10" (25.4 cm)

12" (30.5 cm)

INTERIOR

WALL SHIELD