F120 ROOM AIR CLEANING SYSTEM

68-3042-2

2

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed specifica-
tions. This product is tested and calibrated under
closely controlled conditions, and some minor differ-
ences in performance can be expected if those con-
ditions are changed.

Model:
F120

consists of:

—two filtered return modules with a return grille, prefilter,

and

—either a 99.97% HEPA filter or a 95% DOP filter and

CPZ module;

—four air supply modules with supply grilles;
—a blower module with a two-speed blower, four

recirculating air supply openings, four recirculating air
return openings and an optional exhaust opening;

—75 ft (23m) of six-inch diameter flexible duct; 75 ft (23m)

of eight-inch diameter flexible duct;

—mounting hardware kit consisting of 12 mounting

brackets; 40 ft (12m) of 12-gauge high-tensile strength
wire; six standard T- bar mounts; duct tape;

—seven duct collar straps.

Color:
Blower Housing: Unpainted galvanized steel.
Return and Supply Grilles: Off-white

Electrical Ratings:

a

Off is “O”.

Air Flow Capacity:

a

With exhaust option installed.

b

Purchase filters separately.

Filters:
HEPA: High efficiency particulate air (HEPA) filter is 99.97 per-

cent efficient for 0.3 micron particulates when measured
with Military Standard 282 DOP test.

DOP: Hospital-grade DOP filter is 95 percent efficient for 0.3

micron particulates when measured with Military Standard
282 DOP test.

CPZ: Sorbent modules contain 11 pounds of sorbent. Adsorbs

higher molecular weight hydrocarbons and oxidizes acid
gases and lower molecular weight hydrocarbons.

Ambient Temperature Rating:
Shipping and Storage: -20

°F to +150°F (-29°C to +66°C).

Operating: Ambient temperatures

≥90°F (32°C).

Can tolerate 104

°F (40°C) for brief periods.

Sound Output Rating at 3.3 ft (1m):
High Speed: 52 dBA (below ASHRAE noise criteria (NC)

curve specifications for NC45 over speech recognition fre-
quency range of 500 to 2000 Hz).

Low Speed: 45 dBA (below ASHRAE noise criteria (NC) curve

for NC35 over speech recognition frequency range of 500
to 2000 Hz).

Installation Weight:
Blower Module: 63 lb (28.6 kg).
Supply Module: (4 required): 8 lb (3.6 kg).
Return Module without filter (2 required): 24 lb (10.9 kg).
95% DOP Filter/CPZ Module (2 required): 21 lb (9.5 kg).
99.97% HEPA Filter (2 required): 10 lb (4.5 kg).

Shipping Weight:
F120 with 95% DOP Filter and CPZ Module:

207 lb (94 kg).

F120 with 99.97% HEPA Filter:

182 lb (83 kg).

F120A1015: 152 lb (69 kg).
F120A1007: 70 lb (32 kg).

Dimensions:
See Fig. 1.

120 Vac, 60 Hz

240 Vac, 60 Hz

Fan Speed

a

Fan Speed

a

II (high)

I (low)

II (high)

I (low)

Current (A) 7.0

5.5

3.5

2.8

Power (W) 800

695

800

695

Model

Voltage

Efficiency

Gas, VOC, Odor

Control Module (2)

Air Vol cfm

(cu m/hr)

Air

Vol cfm

(cu m/hr)

a

Particulates at 0.3

micron (DOP Test)

VOC/Odors

(First Pass Average)

F120A 1023 120 Vac 60 Hz

95%

85%

CPZ

900 (1530)

1050 (1780)

F120A 1031 120 Vac 60 Hz

99.97%

900 (1530

1000

(1700)

F120A 1015 120 Vac 60 Hz

b

b

b