Follow the procedure below to personalize and
configure the thermostat according to the heating/
cooling system.

n

Press

and

simultaneously (for three

seconds) until the display appears as shown
on the right.

o

Press

or

to change the option.

p

Press

and

for one second to advance to

the next function.

q

When the last function is displayed, press

and

for three seconds to save any changes

and exit the menu.

NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat
automatically saves any changes made and exits the menu. For programmable models only, at any
time you can save the changes and exit by pressing the Run button.

1

Depending on your thermostat model or your system type, some functions are non-available or

non-applicable.

2

Damage can occur if the compressor is restarted too soon after shutdown. This feature forces the

compressor to wait 5 minutes before restarting. During the wait time, the message Cool On or Heat On
flashes on the screen. When the safe wait time has elapsed, the message stops flashing and the compressor
turns on.

3

Adaptive Intelligent Recovery™ allows the thermostat to “learn” how long your furnace or air conditioner

takes to reach the set temperature. Simply program the desired times and desired temperatures into the
schedule. The thermostat will determine when to activate heating or cooling so that the desired temperature
is attained at the desired time.

4

In Indoor mode, the minimum setpoint is 40°F (5°C) for frost protection. In Garage mode, the minimum

setpoint is 35°F (1.5°C) for energy savings.

Installer setup

Function

1

Default

setting

Options

1

Temperature display format

0

0: Fahrenheit
1: Celsius

2

Time display format

0

0: 12-hour display
1: 24-hour display

3

Heating cycles per hour

5

2 to 6 cycles per hour
• 2: 30 min (steam, gravity)
• 3: 20 min (hot water, 90%+ high-efficiency furnace)
• 4: 15 min (gas or oil)
• 5: 12 min (gas or oil)
• 6: 10 min (electric)

4

Cooling cycles per hour

3

2 to 6 cycles per hour

5

Compressor protection

2

1

0: Off
1: On

6

Adaptive Intelligent Recovery

3

1

0: Off
1: On

7

Application

4

0

0: Indoor mode: 40°F to 90°F (4.5°C to 32°C)
1: Garage mode: 35°F to 90°F (1.5°C to 32°C)