Step 7 gas pressure requirements, Step 8 wiring the fireplace – Hearth and Home Technologies 6000TRS-CE User Manual

Page 31

Advertising
background image

31

A tap is provided on the outlet side of the gas control
for a test gauge connection to measure the manifold
pressure. To measure inlet pressure, provisions
must be made to attach a test gauge to the tap
immediately upstream of the gas supply connection
to the fireplace.

The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system
during any pressure testing of the system at test
pressures in excess of 60 mbar.

If the fireplace must be isolated from the gas supply
piping system by closing an individual shut-off valve,
it must be of the handle-less type.

Pressure requirements for Heat & Glo gas fireplaces
are shown in the table below.

Step 7
Gas Pressure
Requirements

______________________________________________________________

Natural Gas Propane

Butane

Natural Gas

(G20)

(G31)

(G30)

(G25)

Inlet Pressure

20mbar

37 or 50mbar 30 or 50mbar 25mbar

Manifold Pressure

4-8.7mbar

15.7-25mbar 15.7-25mbar

4-8.7mbar

Gas Rate

.54

m3

/

h

.24

m3

/

h

.16

m3

/

h

.54

m3

/

h

Max.Input(NETCV)

10.0 kW

10.0 kW

9.5 kW

8.5 kW

Burner Injector

DMS 33

1.8 mm

DMS 51

DMS 33

Pilot Injector

51

30

30

51

Step 8
Wiring the
Fireplace

NOTE: Electrical wiring must be installed by a
competent electrician.

For Standing Pilot Ignition Wiring
Appliance Requirements

Optional Accessories

Optional remote control
kits require that 230 VAC
be wired to the factory in-
stalled junction box be-
fore the fireplace is per-
manently installed.

Wall Switch

Position the wall switch in the desired position on a wall. Run a maximum of 780cm
or less length of 0.102 cm diameter minimum wire and connect it to the fireplace
ON/OFF switch pigtails.

!

WARNING: DO NOT CONNECT 230 VAC
TO THE GAS CONTROL VALVE OR THE

APPLIANCE WILL MALFUNCTION AND THE
VALVE WILL BE DESTROYED
.