HEATMASTER CONTROL SETTINGS

Description

The 71/101 series is fitted with an electronic controller (MCBA)
which controls burner operation (ignition, safety and modulation),
and provides facilities to adapt the controller to the desired application.

The MCBA has three levels of settings : manufacturer, installer and
user. There are three temperature detectors located in the primary
and secondary circuits.

It provides two operating modes.

1. Heating mode
Temperature set by the user at between 60 and 90 °C.

Differential “ON”, burner starts.

• Differential

“OFF”,

burner

stops.

PI (Proportionnel Integral) regulator in “heating” mode.

The regulator compares the primary temperature with the setting
and modulates.

The room thermostat detects the heating demand

2. Hot water mode

(with hot water priority)

The detector located in the secondary tank detects the hot water
demand.
When a draw-off is detected the controller goes to “hot water
demand” mode:

The primary shunt pump starts.

The heating pump switches off.

• The burner starts and the controller uses the data from the

primary detector to control modulation.

User-accessible parameters

1.

“Hot water” setting adjustable from 20 to 90 °C.

2.

“Hot water” mode: ON/OFF.

3.

“Heating” mode: ON/OFF.

4.

“Heating” setting adjustable from 60 to 90 °C.

Parameters accessible in servicing

Main default settings:
- Hot water priority active.
- Heating demand detection by room thermostat.
- A single heating circuit.

An access code is required for “service” access.

For more technical information, contact your ACV dealer.

TECHNICAL SPECIFICATION

MAXIMUM OPERATING CONDITIONS

Maximum service pressure

(tank full of water)

- Primary circuit: 3 bar
- Secondary circuit: 10 bar

Test pressure

(tank full of water)

- Primary circuit: 4.5 bar
- Secondary circuit: 13 bar

Operating temperature
Maximum temperature: 90 °C

Water quality
• Chlorures: < 150 mg/l (304)

< 2000 mg/l (Duplex)

• 6

ph

8

DOMESTIC HOT WATER PERFORMANCES

HM 71

HM 101

Peak delivery at 40 °C

L/10’

646

905

Peak delivery at 45 °C

L/10’

543

777

Peak delivery at 60 °C

L/10’

346

514

Peak delivery at 70 °C

L/10’

268

385

Peak delivery at 80 °C

L/10’

203

290

Peak delivery at 40 °C

L/60’

2133

3172

Peak delivery at 45 °C

L/60’

1794

2680

Peak delivery at 60 °C

L/60’

1219

1813

Peak delivery at 70 °C

L/60’

971

1378

Peak delivery at 80 °C

L/60’

710

1003

Continuous delivery at 40 °C

L/60’

1835

2776

Continuous delivery at 45 °C

L/60’

1573

2379

Continuous delivery at 60 °C

L/60’

1067

1665

Continuous delivery at 70 °C

L/60’

715

1241

Continuous delivery at 80 °C

L/60’

675

903

Reheat time to 60 °C

min

16

13