RECOMMENdEd MINIMUM WIRE gAUgE FOR ExTENsION CORds*

(120 OR 240 VOlT)

NAMEPlATE

AMPEREs

(at full load)

ExTENsION CORd lENgTH

25 Feet

50 Feet

75 Feet

100 Feet 150 Feet

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

TAblE A

* based on limiting the line voltage drop to five volts at 150% of the rated amperes.