Venting and clearances – Harman Stove Company PF 100 User Manual

Page 13

Advertising
background image

13

PF100

Clearances to combustibles

If installing the furnace in a room separated from the

remaining living spaces, the minimum size of the room must

be no smaller than 8’ x 8’. See Fig. 21. The reason for this
is heat build-up and required space for service and normal
operation.

This is the minimum size of the room even if it is built

of non-combustible material.

High and low air vents MUST be installed between

the room and the remaining living space. Each vent should
be at least 72 square inches in area. ( The vent size will
need to be increased if there is no return air ducting sys-
tem.)

The striped areas are the minimum clearances to com-

bustibles which is 36” from stove body, not hopper or
blower.

The shaded area indicates the required floor protec-

tion area. The PF100 requires 48” x 52” of floor protec-
tion centered around the skidplate footprint. Flooring should
be a minimum of 26 gauge sheet metal covering the instal-

lation clearance area and 18” in front of, and 8” to either
side of the ash pan door.

The 18” clearance on the hopper end is a manufactur-

ers recommendation for adding pellets and or servicing the
feeder mechanism.

The minimum ceiling height is 6’6”. This is set by the

clearance to combustibles ( 28” ) from the top of the
of the furnace. See Fig. 22.

The minimum clearance to the top of the plenum is 4”.
Note the minimum height to the bottom of the supply

duct if it crosses the hopper.

The minimum duct configuration to a living space above

the furnace is as shown in below. An offset of at least 24”
MUST be installed between the plenum and the floor regis-
ter. The register size MUST have an area of at least 240
square inches.

CAUTION: When installing a floor
register, the temperature of the
discharge air MUST be taken into
consideration (The discharge air
temperature may be high enough to
cause burns if not properly operated
and maintained.)

CAUTION: The Blower Motor full
load AMPS MUST be checked.A
plenum damper may be required to
adjust the motor full load AMPS to the
motor nameplate rating.

Fig.21

Fig. 22

18”

52

lon

g

PF100

Skidplate

Footprint

Floor Protector

48” wide



NOTE: Install vent at clearances
specified by the vent manufacturer.

Venting and Clearances