Caution, Installation – Honeywell 191108AC User Manual

Page 2

Advertising
background image

69-0638—1

2

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could cause a hazardous condition.

2. Installer must be a trained experienced service technician.
3. After installation is complete, check out product op-

eration as provided in these instructions.

IMPORTANT: An incorrectly leveled subbase will cause

the temperature control to deviate from setpoint. It is
not a calibration problem.

CAUTION

1. Disconnect power supply to prevent electrical

shock or equipment damage.

2. To prevent interference with the thermostat

linkage, keep wire length to a minimum and run
wires as close as possible to the subbase.

3. Do not overtighten thermostat captive mount-

ing screws because damage to subbase threads
can result.

4. Do not short across coil terminals on relay. This

can burn out the thermostat heat anticipator.

LOCATION

Locate thermostat about 5 ft [1.5m] above the floor in an

area with good air circulation at average temperature.

Do not mount the thermostat where it may be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall

behind the thermostat.

Run wires from the heating, cooling or heating/cooling

equipment to the new thermostat location.

Refer to the Typical Wiring Diagrams section to deter-

mine the number of wires required for your application.

UNPACK THERMOSTAT

Handle your new thermostat carefully; rough handling

may interfere with its accuracy. Before unpacking, refer to
Fig. 1.

Remove and discard the shipping wrap.

IMPORTANT: Save package of screws and instructions

for the homeowner.

Remove the thermostat cover by lifting from the bottom.

Set aside cover until needed later.

Carefully remove the material protecting the mercury

switch bulb.

Loosen two captive mounting screws and separate wall-

plate (if provided) from the back of the thermostat base.

MOUNT WALLPLATE OR SUBBASE
Wall Mounting (Fig. 2)

Hold wallplate or subbase in position on the wall (Fig. 2).
Mark holes on the wall for anchors. Use spirit level to

make sure the wallplate or subbase is level.

Drill 3/16-in. holes, and gently tap anchors into holes

until flush with the wall.

Fig. 1—Unpack thermostat.

12

6

3

9

50

60

70

80

THERMOSTAT
COVER

LIFT
COVER

CAPTIVE
MOUNTING
SCREWS

THERMOSTAT
BASE

M1518

Pull wires through the large wiring hole in the wallplate or

subbase.

Loosely fasten the wallplate or subbase to the wall with

the three screws. Do not completely tighten the screws.

Carefully level the wallplate or subbase (Fig. 3), and

firmly tighten the screws.

Fig. 2—Mounting wallplate or subbase to wall.

M1552A

AUTO

OFF

COOL

HEAT

ON

FAN

R

G

O

W

Y

B

3 SCREW HOLES
WITH PLASTIC
ANCHORS

HEATING/COOLING SUBBASE

3 SCREW HOLES
WITH PLASTIC
ANCHORS

WALLPLATE

M1815

Advertising