Model CBC/CBR-103,104,105,106,107

3-5. PROGRAMMING

1. Press and hold for 4 seconds. The “DEF/SET” light

flashes in display.

Temperature Setpoint
2. Press the

or

to change the temperature setpoint,

within 5 seconds. After 5 seconds, the last entered setpoint
stays in memory.

Other Parameters
3. Press to access the other parameters. Each press of the

accesses the next parameter. The parameters are:

d: (differential) (-15...15 range)

LS: lower set; lower user-access setpoint limit
(-55...99 range)

The units are programmed to defrost 3 times a day, at 8
hour intervals, lasting 30 minutes. Do not program the
setpoint temperature below 33° F (1° C), or ice build-up
will decrease efficiency.

HS: (higher set) upper user-access setpoint limit
(-55...99 range)

CA: (calibration) temperature readout offset to allow for
possible error due to probe location. (-15...15 range)

rP: (relay protection) elect relay status in case of probe defect.
“on” = compressor ON in case of probe defect
“of” = compressor OFF in case of probe defect

PS: (protection system-short cycle) select type of compressor
protection desired (the actual time delay is set with the next
parameter):

“0”=delay before start - in seconds
“1”=delay before start - in minutes
“2”=delay after stop - in minutes
“3”=delay between starts - in minutes

Pt: (protection time) select the time delay setting for compres-

sor protection. (0...31 range)

3-5