Warning, Caution – Honeywell FAST-ACTING User Manual

Page 2

Advertising
background image

ML4202, ML4302, ML4702, ML4802, ML8202, ML8302 FAST-ACTING, TWO-POSITION ACTUATORS

62-0194—3

2

Controller Type:

ML4202, ML4302: Line voltage (120 Vac), two-position, spst

(Series 40).

ML4702, ML4802: Line voltage (230 Vac), two-position, spst

(Series 40).

ML8202, ML8302: Low voltage (24 Vac), two-position, spst

(Series 80).

Accessories:

201391 Shaft Adapter for 3/8 in. shafts (not supplied with

actuator).

205649 Mounting Bracket (not supplied with actuator).

32003532-005 Dual Auxiliary Switch Package for high-

temperature applications.

Table 2. Approvals.

WARNING

Electrical Power Hazard.

Line voltage can cause death or serious injury

and short equipment circuitry.

Disconnect power supply before installation.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Low voltage can shock individuals or short

equipment circuitry.

Disconnect power supply before installation.

CAUTION

Equipment Damage Hazard.

Tightly securing actuator to damper housing can

damage actuator.

Mount actuator to allow it to float along its vertical axis.

CAUTION

Actuator Damage Hazard.

Using actuator as shaft bearing causes device

damage.

Use actuator only to supply rotational torque. Avoid

any side loads to actuator output coupling bearings.

IMPORTANT

1. All wiring must comply with local electrical codes,

ordinances and regulations.

2. Voltage and frequency of transformer used with

ML8202 and ML8302 must correspond with the

characteristics of power supply and actuator.

3. Use wires rated for at least 75°C (167°F).

4. For actuators with a product date code before 0527,

a power break of less than two seconds can cause

the actuator to spring-return 5 degrees or less and

remain in place until a power break of longer dura-

tion. For actuators with a product date code of 0527

or after, a power break of any duration will cause the

actuator to spring-return and be able to drive imme-

diately when power is reapplied.

Fig. 1. ML4202, ML4302, ML4702, ML4802, ML8202,

ML8302 dimensional drawing in in. (mm).

Fig. 2. Typical 24 Vac wiring.

Fig. 3. Typical 120 Vac wiring.

Fig. 4. Typical 230 Vac wiring.

ML4202

ML4302

ML4702

ML4802

ML8202

ML8302

UL/cUL

X

X

X

UL873 Plenum Rating, File

No. E4436; Guide No. XAPX.

X

X

X

CE

X

X

C-TICK

X

1 (25)

5/8

(17)

6-3/8

(161)

7-1/2

(192)

4 (102)

7/8 (22)

/ (

)

2 (51)

3-5/16 (84)

1/16 (2

L1

24 VAC

L2

RED
BLACK

M17585A

( )

( )

L1

120 VAC

L2

WHITE

BLACK

M17589A

( )

( )

L1

230 VAC

L2

BLUE

BROWN

M17588A

( )

( )