Caution, Adjust fan operation switch, as required, Adjust system on-time, as required – Honeywell D User Manual

Page 2: Wiring thermostat, T8112c,d electronic programmable thermostats

Advertising
background image

69-0917—2

2

T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS

1. Remove mounting plate from the wall, and drill

3/16 inch holes in wall (if drywall) as marked. For
firmer material such as plaster or wood, drill
7/32 inch holes. Gently tap anchors (provided) into
drilled holes until flush with the wall.

2. Reposition mounting plate over holes, pulling

wires through wiring opening. Loosely insert two
mounting screws into holes.

3. Level for appearance only; the thermostat will

function properly even when not level. Tighten
mounting screws. See Fig. 2.

IMPORTANT

When using a high efficiency furnace such as a
90 percent or greater AFUE (Average Fuel
Utilization Efficiency) unit, adjust screw A out
one turn and screw B in.

LEVEL

M1714A

Fig. 2. Leveling mounting plate.

Adjust Fan Operation Switch,
as Required

The Thermostat fan operation switch, labeled FUEL
SWITCH is factory set in the F position. See Fig. 4. This
is the correct setting for most systems. If your system is
an electric heat system, set the switch to E. The E setting
allows the fan to turn on immediately with the heating or
cooling in a system where the G terminal is connected.

Adjust System On-time, as Required

The system on-time is factory-set for a warm air, gas or
oil heating system. If you are installing it on another type
of system, the system on-time must be adjusted
accordingly by setting screws A and B on the back of the
thermostat. Use the heating system table shown in Fig. 3
as a guide. The system on-time should be optimized
according to the type of system to minimize room
temperature swings. Setting the screw

out one turn

means turning the screw approximately 360

°

or one

complete turn. Setting the screw

in means tightening the

screw completely down.

In the event that you want longer furnace on-time,
readjust the screws A and B as follows:

Warm Air Furnace—set at the Hot Water setting (A—
out one turn, B—in).

Electric Furnace—Leave at the Warm Air Furnace
setting (A—in, B—in).

NOTE:

This thermostat does not have a setting for
steam/gravity air. Cycles would not be long
enough for accurate temperature control.

M3669

R

Rc

W Y G

B D

A C

THERMOSTAT BACK

FOR HIGH EFFICIENCY FURNACE (90%+ AFUE)

SCREW A–OUT 1 TURN
SCREW B–IN
FUEL SWITCH – F POSITION

F

E

FUEL SWITCH

WARM AIR
FURNACE

A–IN

ADJUST SCREWS THROUGH HOLES

TO SELECT OPERATION DESIRED

B–IN

FUEL SWITCH

POSITION

HEATING SYSTEM

ELECTRIC
FURNACE

HOT WATER
BOILER

A–IN

A–OUT
1 TURN

B–IN

B–OUT
1 TURN

E

F

F

ADJUST:

Fig. 3. Back view of thermostat.

Wiring Thermostat

All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 4 through 7 for typical hookups. A
letter code is located near each terminal for identification.
See Table 1 for terminal cross referencing information.

CAUTION

Disconnect power before wiring to prevent
electrical shock or equipment damage.

1. Connect the system wires to the thermostat. See

Fig. 8. A letter code is located near each terminal
for identification.

NOTE:

Hold the thermostat as shown in Fig. 9 to
minimize need for wire extenders.

2. Securely tighten each terminal screw.

3. Push excess wire back into the hole.

4. Plug hole with nonflammable insulation to prevent

drafts from affecting the thermostat.

Table 1. Typical Wire Colors and Functions

a

Wire colors are typical; verify at heating/cooling
equipment connection.

Thermostat

Terminal

Connect to

Wire Color

a

Function

G

Green

Fan

Y

Yellow

Cooling

W

White

Heating

Rc

Blue

Air Cond. Power

R

Red

Furnace Power

Advertising