F. install attic insulation shield – Heat & Glo Fireplace BAY-40 User Manual

Page 29

Advertising
background image

29

3 in. (76 mm)

overlap

Insert three

screws

Bend inward

90°

Bend remaining tabs
to rest against pipe to
prevent insulation
from falling in.

Figure 8.6 Prepare Attic Insulation Shield

Installation of a ceiling fi restop is required

• Refer to Figures 8.6 - 8.8.

• Roll the shield (around the chimney if already installed)

until you have a 3 in. (76 mm) overlap and the three
holes on each side match up (large holes on top).

• Insert three screws into the matching holes to form a

tube.

• Bend three tabs on the bottom of the tube inward to 90°

to maintain chimney air space (refer to Figure 8.6).

• Rest the insulation shield on the ceiling fi restop below.
• Bend the three short tabs at the top of the shield inward

to 90° to maintain the 2 in. (51 mm) air space from the
chimney.

• Bend the remaining top tabs to just meet the pipe.

F. Install Attic Insulation Shield

WARNING! Risk of Fire! You MUST install an attic insu-
lation shield when there is any possibility of insulation or
other combustible material coming into contact with the
chimney.
DO NOT pack insulation between the chimney and the

attic insulation shield.

• Failure to keep insulation and other materials away from

chimney pipe could cause fi re.

DO NOT offset chimney inside insulation shield.

If you wish to make a custom shield or barrier, follow
these guidelines:

• Metal is preferred, although any material stiff enough to

hold back the insulation can be used.

WARNING! Risk of Fire! Use of cardboard or other
materials that can defl ect under humidity or other envi-
ronmental conditions is not recommended.

• The shield or barrier must be tall enough to extend

above the insulation and prevent blown-in insulation
from spilling into the cavity.

• Maintain

specifi ed air spaces around chimney.

• Check instructions and local codes for further details.

Heat & Glo • BAY-40, PIER-40 • 34977 • Rev V • 11/08

6 Tabs bent

in 90°

Tabs bent in to

rest against pipe

Attic Insulation Shield

Ceiling Firestop

13 in.

(330 mm)

17 in. (432 mm)

diameter

Insulation

Insulation

Pipe

Pipe

Figure 8.7 Install Attic Insulation Shield (fi restop above ceiling)

6 Tabs bent

in 90°

Tabs bent in to

rest against pipe

Attic Insulation Shield

Ceiling Firestop

13 in.

(330 mm)

17 in. (432 mm)

diameter

Insulation

Insulation

Pipe

Pipe

Figure 8.8 Install Attic Insulation Shield (fi restop below ceiling)