Super-Magnum Coal Stoker Stove

Do Not Burn Wet Coal!

3-90-02702R6_03/13

E. Draft Test Procedure

Because of the dangers associated with coal gases and

the potential for carbon monoxide release, It is important to

balance the airflow into the stove with the draft in the flue.

The combustion blower has a restrictor plate attached to it,

which must be adjusted upon completion of the installation.

The barometric damper, if installed, must also be set to

prevent over-drafting in the appliance. Follow these steps to

ensure safe and efficient operation of your Super Magnum

coal stoker stove.

You will need to start a fire in the appliance to establish

a draft in the chimney flue. Refer back to these

instructions after reading the entire manual.

• Drill a hole into the flue connector pipe, for the purpose

of attaching a draft meter. This hole should be between

the barometric damper and the stove's flue collar, and in

an inconspicuous location, as it will be closed off after

the test with a bolt.

• Attach the draft meter to the hole in the connector. A great

chimney will have draft without a fire or heat source. Set

the barometric damper to maintain -.06 to -.08 (inches of

water column).

• Remove the draft meter from the connector pipe and seal

the hole by threading in a screw or bolt. You may also

want to apply a small dab of high-temperature silicone to

the threads prior to installing.

• Next, remove the set-screw plug bolt from the front of the

Super Magnum body. This plug is located in the center,

just below the top load door. Attach the draft meter hose

to the stove.

• Turn the feed adjuster knob to "Test". This will run the

combustion blower at its highest possible voltage or

speed.

• Close the restrictor over the opening to the combustion

blower until the draft reading in the firebox fits the -.03 to

-.04 range. This will ensure that the combustion blower

will never push more air into the firebox than the draft in

the flue is capable of removing.

• Disconnect the draft meter from the stove and re-install

the set screw plug bolt.

Draft meter

connection

locations

Do not operate if the draft in the flue

exceeds -.08 in water column.

WARNING

!