Recovery ratings and amperage at selected kw, Electrical, Marine products division – Hubbell MSH User Manual

Page 6

Advertising
background image

6

Recovery Ratings And Amperage At Selected KW

KW

INPUT

BTU/HR

RATING

Gallons Per Hour (GPH) Heated At

Various Temperature Rises

Amperage Rating At Various Voltages

60 °F

Δ

80 °F

Δ

100 °F

Δ

120 °F

Δ

140 °F

Δ

208V 3F

240V 3F

380V 3F

440V 3F

480V 3F

15

51,195

103

77

62

51

44

42

36

23

21

18

20

68,260

137

103

82

68

59

56

48

30

28

24

25

85,325

171

128

103

85

73

69

60

38

35

30

30

102,390

205

154

123

103

88

83

72

46

42

36

35

119,455

239

179

144

120

103

97

84

53

49

42

40

136,520

273

205

164

137

117

111

96

61

56

48

45

153,585

308

231

185

154

132

125

108

68

63

54

50

170,650

342

256

205

171

146

139

120

76

70

60

55

187,715

376

282

226

188

161

153

132

84

77

66

60

204,780

410

308

246

205

176

167

145

91

84

72

65

221,845

444

333

267

222

190

181

157

99

91

78

70

238,910

478

359

287

239

205

195

169

106

97

84

75

255,975

513

384

308

256

220

208

181

114

104

90

80

273,040

547

410

328

273

234

222

193

122

111

96

85

290,105

581

436

349

290

249

236

205

129

118

102

90

307,170

615

461

369

308

264

250

217

137

125

108

95

324,235

649

487

390

325

278

264

229

145

132

114

100

341,300

683

513

410

342

293

278

241

152

139

120

110

375,430

752

564

451

376

322

306

265

167

153

132

120

409,560

820

615

492

410

351

333

289

183

167

145

125

426,625

854

641

513

427

366

347

301

190

174

151

150

511,950

1025

769

615

513

439

417

361

228

209

181

175

597,275

1196

897

718

598

513

486

421

266

244

211

200

682,600

1367

1025

820

683

586

556

482

304

279

241

225

767,925

1538

1153

923

769

659

625

542

342

313

271

250

853,250

1708

1281

1025

854

732

695

602

380

348

301

275

938,575

1879

1409

1128

940

805

764

662

418

383

331

300

1,023,900

2050

1538

1230

1025

879

834

723

456

418

361

325

1,109,225

2221

1666

1333

1110

952

903

783

494

453

391

350

1,194,550

2392

1794

1435

1196

1025

973

843

532

487

421

375

1,279,875

2563

1922

1538

1281

1098

1042

903

570

522

452

400

1,365,200

2733

2050

1640

1367

1171

1112

963

608

557

482

450

1,535,850

3075

2306

1845

1538

1318

1251

1084

685

627

542

500

1,706,500

3417

2563

2050

1708

1464

1390

1204

761

696

602

1000

3,412,000

6833

5125

4100

3417

2929

2779

2408

1521

1393

1204

1200

4,094,400

8200

6150

4920

4100

3514

3335

2890

1825

1671

1445

1400

4,776,800

9567

7175

5740

4783

4100

3891

3372

2130

1950

1686

1600

5,459,200

10933

8200

6560

5467

4686

4446

3854

2434

2229

1927

KW x 1000

÷

1.73 = Amps 3

Φ

Volts

KW x 1000 = Amps 1

Φ

Volts

Electrical

Notes: The KW selections above are shown for convenience. A full selection of KW ratings from 1 to 1600 KW is available by entering the

desired KW into the model number. For alternate voltages including 415, 575 and 600 volt, please consult factory.

Note: Each branch

circuit is rated at

a maximum of 48

Amps and each

circuit is typically

operated as an

independent

temperature step.

150 x 1000

÷

1.73 = 180 Total Amp Draw

480
180 ÷ 48 Amps max circuit rating = 3.75

Round up the number of circuits to 4

Example:

150 KW at 480V 3F

Marine Products Division

Advertising