S8701/S8702 DIRECT SPARK IGNITION CONTROLS

Fig. 4. S8701/S8702 Sequence of Operation for 1 Trial Models (B, D, J, and K Models).

START

PREPURGE

(J AND K MODELS ONLY)

SAFE START CHECK

TRIAL FOR IGNITION

MAIN BURNER
OPERATION

END

THERMOSTAT CALLS FOR HEAT

SAFE START CHECK. LED BLINKS RAPIDLY.

PREPURGE - J & K MODELS ONLY

SPARK GENERATOR POWERED
MAIN VALVE OPERATORS OPEN.

IF NO SPARK, B, D, J, AND K MODELS GO INTO LOCKOUT
AFTER ONE (1) TRIAL FOR IGNITION PERIOD.
ALARM CIRCUIT IS ACTIVATED.
LED IS ON STEADY. SYSTEM MUST BE RESET.

IF FLAME CURRENT SENSED:

(MUST BE SENSED AT BOTH
BURNERS ON S8702)
SPARK GENERATOR IS SHUT OFF.
LOCKOUT TIMER IS RESET.

IF FLAME CURRENT IS NOT SENSED:

B, D, J, AND K MODELS GO INTO LOCKOUT
AFTER ONE (1)TRIAL FOR IGNITION PERIOD.
LED IN ON. SYSTEM MUST BE RESET.

MAIN BURNER OPERATION
UNIT MONITORS BURNER
FLAME CURRENT.

LOSS OF FLAME

SPARK GENERATOR IS POWERED.
B, D, J, AND K MODELS GO INTO LOCKOUT AFTER
ONE (1) TRIAL FOR IGNITION PERIOD. LED IS ON STEADY.
SYSTEM MUST BE RESET.

TEMPERATURE CONTROLLER
IS SATISFIED.
POWER TO UNIT IS INTERRUPTED.
VALVES CLOSE.
MAIN BURNER(S) ARE OFF.

DURING NORMAL OPERATION LED BLINKS ONCE PER SECOND.

M18058

NOTES: B, D, J, AND K MODELS GO THROUGH ONE (1) TRIAL FOR IGNITION PERIOD BEFORE LOCKOUT.

LOCKOUT = VALVE CLOSED PLUS SPARK OFF PLUS ALARM ACTIVATED PLUS LED ON STEADY.