Scaleplate adjustment, Checkout – Honeywell PRESSURETROL L404T User Manual

Page 7

Advertising
background image

L404F,T,V PRESSURETROL

®

CONTROLLERS

7

71-2429—06

Fig. 12. view of L404 PressureTrol

®

Controller.

Scaleplate Adjustment

The L404F,T,V has been carefully calibrated during

manufacture and should not require recalibration.

However, if recalibration is necessary, remove the cover and

loosen the setscrews which hold the scaleplate. Adjust the

plate up or down, as required, to bring the device into

calibration. Tighten the setscrews securely and replace the

cover.

CHECKOUT

After the controller has been installed, wired and adjusted, it

should be tested with the system in operation. First, allow the

system to stabilize. Then, observe the operation of the

controller while raising and lowering its setpoint. Pressure

should increase when the setpoint is raised and decrease

when the setpoint is lowered.

Also, check the make and break points of the controller. If they

do not agree with a separate, accurately calibrated pressure

gauge, a slight adjustment of the scaleplate(s) may be

necessary.

Use accurate pressure testing equipment when checking out

the controller. Do not rely on inexpensive gauges. The

controllers are carefully calibrated at the factory.

GROUND SCREW

DIFFERENTIAL

ADJUSTING SCREW

SCALEPLATES

DIAPHRAGM

ASSEMBLY

M19640A

OPERATING

LEVER

MAIN SCALE

PRESSURE

INDICATOR

DIFFERENTIAL

SETTING

INDICATOR

PRESSURE ADJUSTING SCREW