Heatcraft Refrigeration Products H-IM-72A User Manual

Page 35

Advertising
background image

35

Symptom

Cause

Remedy

Low

1.

Insufficient refrigerant in system

1.

Check for leaks. Repair and add charge

discharge

2.

Faulty condenser temp. regulation

2.

Check condenser control operation

pressure

3.

Compressor suction or discharge valve

3.

Clean or replace leaky valve plates

inefficiencies.

4.

Low suction pressure

4.

See corrective steps for low suction pressure

5.

Head pressure control valve set wrong

5.

Adjust valve or install a head pressure

or no head pressure control valve

control valve.

High suction

1.

Excessive load

1.

Reduce load or add additional equipment

pressure

2.

Expansion valve overfeeding

2.

Check remote bulb. Regulate superheat.

Low suction

1.

Lack of refrigerant

1.

Check for leaks. Repair and add charge

pressure

2.

Evaporator dirty or iced.

2.

Defrost or clean coil

3.

Clogged liquid line filter drier

3.

Replace cartridge(s)

4.

Clogged suction line or compressor

4.

Clean strainer or replace filters

suction strainer

5.

Expansion valve malfunctioning

5.

Check and reset for proper superheat

6.

Condensing temperature too low

6.

Check means for regulating

condensing temperature

7.

Improper TXV

7.

Check for proper sizing

Little or No

1.

Clogged suction oil strainer

1.

Clean

oil pressure

2.

Excessive liquid in crankcase

2.

Check crankcase heater. Reset TXV for
higher superheat. Check liquid line solenoid
valve for proper operation.

3.

Low oil pressure safety switch defective

3.

Replace

4.

Worn oil pump

4.

Replace

5.

Oil pump reversing gear stuck in

5.

Reverse direction of compressor rotation

the wrong position.

6.

Low oil level

6.

Determine where the oil is or add oil.

7.

Worn bearings

7.

Replace compressor

8.

Loose fitting on oil lines

8.

Check and tighten fittings

9.

Pump house gasket leaks.

9.

Replace gasket

Compressor

1.

Lack of refrigerant

1.

Check for leaks. Repair and add charge

loses oil

2.

Excessive compression ring blowby

2.

Replace compressor

3.

Refrigerant floods back

3.

Maintain proper superheat at compressor

4.

Improper piping or traps

4.

correct piping

Compressor

1.

Operating beyond design limits

1.

Add facilities so that conditions are within

thermal

allowable limits.

protector

2.

Discharge valve partially shut

2.

Open valve

switch open

3.

Blown valve plate gasket

3.

Replace gasket

4.

Dirty condenser coil

4.

Clean coil

5.

Overcharged system

5.

Reduce charge