Settings, Checkout – Honeywell Q539A User Manual

Page 3

Advertising
background image

Settings

SUBBASE SETTING

The subbase switching positions control the system

operation as described below.

SYSTEM SWITCH (some subbases do not have all of the

following functions):
COOL—cooling system is automatically controlled

by the thermostat. Heating system is off.

OFF—both the heating and cooling systems are off. If

the fan switch is at AUTO position, the cooling fan
is also off.

HEAT—heating system is automatically controlled

by the thermostat. Cooling system is off.

FAN SWITCH:

ON—fan operates continuously.
AUTO—fan operates with cooling equipment as con­

trolled by the thermostat or with the heating equip­
ment as controlled by the plenum switch.

To move the subbase switches to the desired control

positions, use thumb and index finger to slide lever. Stop
lever must stop over desired function indicator position for
proper circuit operation.

Fig. 4—Typical hookup for Q539H in heating­
cooling application with remote switching
required to select heating or cooling and to
provide automatic fan operation.

Q539H/T87F INTERNAL SCHEMATIC

T87F

TEMP.
FALL

R1

ADJUST-
ABLE
HEAT
ANTICIPATOR

FILTER
LIGHT

X

W

Y

G

R

CLOGGED
FILTER SWITCH
OR COOLING
PANEL
CONNECTION

HEATING
RELAY OR
VALVE
COIL

COOLING
CONTACTOR
COIL

EXTERNAL
SWITCHING
FOR AUTO
FAN

FAN
RELAY

Z

2

1

1

X TERMINAL IS USED ON Q539 MODELS WITH
FACTORY-INSTALLED MALFUNCTION LIGHT.

W1

Y1

AUTO

FAN

ON

HEAT

COOL

REMOTE
SYSTEM
SWITCH

2

POWER SUPPLY. PROVIDE DISCONNECT

L2 L1

MEANS AND OVERLOAD PROTECTION AS REQUIRED.

(HOT)

M8833

Fig. 5—Typical hookup for Q539J in heating­
cooling applications. Fan relay operates
automatically on heat or cool with fan in AUTO
position

Q539J/T87F INTERNAL SCHEMATIC

HEAT

OFF

COOL HEAT OFF COOL AUTO

FAN

ON

W

B

R

G

P

T87F

TEMP.
FALL

R1

ADJUST-
ABLE
HEAT
ANTICIPATOR

FILTER
LIGHT

X

Y

CLOGGED
FILTER SWITCH
OR COOLING
PANEL
CONNECTION

COMPRESSOR
RELAY

COOLING
DAMPER
MOTOR

FAN
RELAY

O

L1
(HOT)

L2

3

2

1

W1

Y1

ELECTRIC
HEAT
RELAY

HEATING
DAMPER
MOTOR

1

2

3

X TERMINAL IS USED ON Q539 MODELS WITH FACTORY-
INSTALLED MALFUNCTION LIGHT.

WITH NO O TERMONAL LOAD, THERMOSTAT CURRENT DURING
HEATING CYCLE VARIES DEPENDING ON WHETHER FAN SWITCH
IS IN THE ON OR AUTO POSITION. HEATER SHOULD BE SET FOR
COMBINED CURRENT LEVEL OF HEAT RELAY AND FAN RELAY COILS.
WITH O TERMINAL LOAD, SET THERMOSTAT HEAT ANTICIPATOR
TO ITS MAXIMUM SETTING. (LIMIT THE THERMOSTAT HEATING
LOAD CURRENT TO 0.8 AMPS TO ASSURE GOOD PERFORMANCE.)

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

M8834

Checkout

When installation is complete, turn on power supply and

check system operation.

HEATING

Move the system switch on the Q539 to HEAT and the

fan switch to AUTO. Move the heating setpoint dial to about
6

AC (10AF) above room temperature. Heating equipment

should start and the fan should run. Change the setpoint to
about 6

AC (10AF) below the room temperature. The heating

equipment and fan should shut off.

NOTE: In heat pump applications, a minimum off-timer

provides a five-minute time delay before starting com­
pressor when the thermostat last turned off the compres­
sor, or when the system first received power. This delay
prevents compressor short cycling.

3

95-6486—9