C. sidewalls/surrounds, D. frame the fireplace – Heat & Glo Fireplace RUTHERFORD 50 User Manual

Page 19

Advertising
background image

19

60-7/8 in.

50 in.

18 1/2 in.
[470 mm]

19 3/4 in.
[500 mm]

4 in.

[102 mm]

50° angle

39° angle

24 in.

[610 mm]

BRICK

FRONT

FLUSH
FRONT

24 in.

[610 mm]

22 3/8 in.
[568 mm]

Note: Grid depicts 1 inch squares.

Figure 6.3 Combustible Mantel Leg or Wall Projections (acceptable on both sides of opening)

C. Sidewalls/Surrounds

• Locate adjacent combustible sidewalls a minimum of 24 in. (610 mm) from fi replace opening.
• Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed per Figure 6.3.

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

• Observe all required air space clearances to combustible materials as shown in Figure 6.2.
• Framing across the top of fi replace must be above top standoffs.

B

C

A

2 in. (51 mm)
min. air space
clearance
from chimney.

Note: Framing must be
extended straight up,
all the way to the ceiling.

Header MUST NOT be notched!

D

D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.

D

Figure 6.4 Framing the Fireplace

Model #

A

B *

C **

D

RUTHERFORD-50

in.

61 7/8

28 3/8

74 1/2

12

mm

1572

721

1892

305

* If interior of chase will be drywalled, add the thickness to this meaurement.

** Adjust header height for raised fl oor under fi replace.

Heat & Glo • RUTHERFORD-50 • 4059-333 Rev D • 07/08