Figure 1

3

D

W

H

cooling

Capacity SEER CFM

80

85

90

95

100

105

110

115

HR18D2VAR HB2400VD1M20

M

17000

13

670

19210 19197 18020 17000

17237

16490

16712 15980

HR24D2VAR HB2400VD1M20

H

22500

13

900

25425 24683 23850 22500 22162.5

21825

21488 21150

HR30D2VAR HB3600VD1M22

L

28000

13

1125 31640 30716 29680 28000

27580

27160

26740 26320

HR36D2VAR HB3600VD1M22

H

35000

13

1240 39550 38395 37100 35000

34475

33950

33425 32900

heating

Capacity HSPF CFM

-10

0

10

20

30

40

50

60

HR18D2VAR HB2400VD1M20

M

15000

7.8

670

4773

6418

8036

9682 11272.73 13264

15627 18000

HR24D2VAR HB2400VD1M20

H

20000

7.8

900

6364

8558

10715 12909

15030

17685

20836 24000

HR30D2VAR HB3600VD1M22

L

26000

7.8

1125

8273

11125 13930 16782

19539

22990

27087 31200

HR36D2VAR HB3600VD1M22

H

32500

7.8

1240 10341 13906 17412 20977

24424

28738

33859 39000

Table 2: System Capacity

Cooling Capacity with different outdoor temperature

Heating Capacity with different outdoor temperature

Outdoor

Indoor

ARI data of indoor

Outdoor

Indoor

ARI data of indoor

Indoor fan

speed

Indoor fan

speed