Warning, Finalizing remote installation, Adjusting “low flame” setting (lp only) – Hearth and Home Technologies RCTS-MLT User Manual

Page 4

Advertising
background image

4

Figure 8.

REMOTE

RECEIVER

JAM NUT

REGULATOR

TOWER

PLUNGER

RED

ORANGE

BLUE

Finalizing Remote Installation

1. Turn the main gas knob ON, relight pilot fl ame, and

turn fi replace ON.

2. Inspect gas connections around solenoid and regulator

tower with a comercially available, non-corrosive leak
check solution.

3. Turn fi replace off and proceed to next section.

4. Light the fi replace as directed in the Owner’s Manual.

5. Adjust “High Flame” by turning solenoid clockwise to

increase pressure and counterclockwise to reduce
pressure. Adjust until the reading on the manometer is
3.5 inches w.c. for natural gas and 10 in w.c. for LP.

6. Tighten jam nut (Figure 4 and Figure 7) to the face of

the regulator tower body.

7. Turn the main gas knob on the gas valve OFF.

8. Remove the manometer from the pressure tap and

tighten the pressure tap closed.

9. Connect blue wires from the solenoid to the orange

wires on the remote receiver box. See Figure 8.

Adjusting “Low Flame” setting (LP ONLY)

1. Using a 5/16 in. slotted screwdriver turn brass screw

inside regulator tower two complete rotations clock-
wise. See fi gure 6.

NOTE: A manometer MUST be used to set the manifold
pressure on the gas valve.

EXPLOSION RISK!
• Adjust lowpoint setting BEFORE installing

fl ame control solenoid on LP units.

WARNING

Installing the Flame Control Solenoid and
Wiring the Flame Controller (NG & LP)

1. Ensure the Flame Control Solenoid is not attached to

the remote control receiver box.

2. Loosen outlet pressure tap and install a manometer.

3. Install Flame Control Solenoid by turning it into the regula-

tor tower fi ve complete rotations clockwise. See fi gure 7.

Figure 7.

2. Loosen outlet pressure tap and install a manometer.

3. Light the fi replace as directed in the Owner’s Manual.

4. Continue to adjust the LP “Low Flame” by turning

brass screw clockwise to increase pressure and coun-
terclockwise to reduce pressure. Adjust until the low
pressure reading on the manometer to 6.3 in. w.c.

5. Proceed to installing Flame Control Solenoid.

Figure 6.

JAM NUT