MEDIA AIR CLEANER

69-1866—01

4

HOW TO INSTALL YOUR MEDIA AIR CLEANER

IMPORTANT:

Due to differences in how furnaces are installed, it is impossible to provide detailed instructions that cover every installa-

tion. The following instructions provide general guidelines on installation of the Media Air Cleaner. It is the responsibility

of the installer to determine how to properly install the Media Air Cleaner in accordance with local codes, standards, and

accepted building practices.

Determine Best Location for Media Air Cleaner

CAUTION

Equipment Damage Hazard. Can damage or

destroy

HVAC equipment.

Only install Media Air Cleaner on the return air duct.

Select a location to mount the media air cleaner on the return

plenum. See Figs. 3 to 9.

• The media air cleaner should be installed such that

all of the air passing through the HVAC system is

circulated through the air cleaner.

• The best location is in the return air duct next to the

blower compartment.

Do not mount in the supply air duct.

• If installing media air cleaner in system with

humidifier, avoid applications where water mist will

reach the filter cartridge.

• The media air cleaner can be mounted in any

position.

• The metal cabinet is strong enough to support the

weight of furnace and evaporator coil.

• Choose a location that is readily accessible for

replacing the filter. Allow at least 26 in. clearance in

front of the unit for removal of the filter cartridge.

Do not install in locations that get colder than -40

°

F

or hotter than 140

°

F.

• Make sure filter pressure drop will not negatively

impact system performance. See Fig. 10.

• Media air cleaner dimensions are given in Fig. 11.

• Make sure the Media Air Cleaner is located at least 3

feet away from any ultraviolet air treatment system,

such as the Honeywell RUVLAMP1.

NOTE: Every installation is unique. Installer is responsible

for ensuring that installation is in accordance with all

local building codes and standards.

Fig. 3. Highboy furnace with side installation. Media air

cleaner is mounted vertically where return enters side

inlet of furnace.

Fig. 4. Highboy furnace with installation beneath furnace.

Media air cleaner is mounted horizontally where return

enters from below.

M13642