E. Combustible Mantel

• Refer to the shaded areas of Figure 11.4 for locations and dimensions of a combustible mantel.

• A combustible mantel may be positioned no lower than 12 5/8 in. (321 mm) above the top of the fi replace opening.

• A combustible mantel may have a maximum depth of 10 in. (254 mm).

• Combustible trim and materials cannot be placed within 6 in. (152 mm) of the fi replace opening (top or sides).

• Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) above the top

of the fi replace opening.

• Combustible trim must not cover the metal surfaces of the fi replace.

• Mantel clearance is in accordance with

Section 7-3.3.3 of ANSI/NFPA211.

Mantel

7 ft (2134 mm)

minimum

base of fireplace

to ceiling

Combustible wall

2 x 4 stud wall
Standoffs

Measured from top of fireplace opening

10 in./254 mm

1 1/2 in./38 mm

maximum

12 5/8 in./321 mm

minimum

12 in./305 mm

minimum

6 in./152 mm

minimum

Combustible

decorative facing

Non-combustible

decorative facing

such as steel, iron,

brick, tile, concrete,

slate, glass, plasters

Seal joint with

non-combustible

sealant

Grid represents

1 in. squares.

Figure 11.4 Clearances to Mantels or other Combustibles above Fireplace

Heatilator • CL36D, CR36D • 12538 • Rev Z 7/12