Hoshizaki KMD-450MAH User Manual

Page 16

Advertising
background image

16

Condenser Return Line

Shut-Off Valve

Condenser Return Line

Drain Valve

Icemaker

Drain Outlet

3/4" FPT

Icemaker

Water Supply

Inlet

1/2" FPT

Condenser

Water Supply

Inlet

1/2" FPT

Condenser

Return Outlet

1/2" FPT

Separate piping to approved drain.
Leave a two-inch (5 cm) vertical air
gap between the end of each pipe
and the drain.

Icemaker

Bin Drain Outlet

3/4" FPT

Two-inch

(5 cm) air

gap

Floor Drain

Bin

Icemaker Water Supply

Line Shut-Off Valve

Icemaker Water Supply Line

Drain Valve

Condenser Water Supply Line

Shut-Off Valve

Condenser Water Supply Line

Drain Valve

b) Connection to a Closed Loop System
• Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD

copper tubing is recommended for the condenser water supply line.

• Condenser return outlet is 1/2" FPT. A minimum of 3/8" OD hard pipe is recommended for

the condenser return line.

• Shut-off valves and drain valves should be installed at both the condenser water supply

inlet and condenser return outlet.

• The water supply to the condenser should not drop below 4 GPM.
• The pressure differential between the condenser water supply inlet and condenser return

outlet must be no less than 10 PSIG.

• When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet

temperature should not drop below 45°F (7°C) and the condenser return outlet
temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker
installation is complete, confirm the condenser return outlet temperature 5 minutes
after a freeze cycle starts. If the outlet temperature is not in the proper range, adjust the
water-regulating valve to bring it into range.

Fig. 9

KMD-450MWH

Connection to a Closed Loop System