TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS

7

75-7134—1

Table 5. TP974A, TP978A-E, TP979A-E Thermostat Specifications.

Old

Model No.

New

Model No.

Action

Setpoint

Supply Air

Pressure
psi (kPa)

Degrees

Throttling

Range

Special Features

TP974A 1000

TP974A 2000

DA, 1- or

2-Pipe Sensor
Bleed Type

50-100

°

F

(10-38

°

C)

Range

18 (124)

3-15 (21-103)

Output

Sensor for use with
RP908 & RP920
Controller

TP978A 1006

No

Replacement

DA Heating
DA Cooling

60-73

°

F

Heating

18 (124)

2-10

°

F

(1.1-5.6

°

C)

ZEB Energy
Conservation, Setpoint
Stop 73

°

F (Heating),

77

°

F (Cooling)

TP978B 1004

No

Replacement

RA heating
DA Cooling

77-90

°

F

Cooling

TP978C 1002

No

Replacement

DA Heating
RA Cooling

TP978D 1000

No

Replacement

RA Heating
RA Cooling

TP978E 1007

TP978E 2007

RA (Right Side)

DA (Left Side)

68-82

°

F

0.18 (1)

1-4

°

F

Includes Cover
Special System-
Powered Thermostat
for Carrier

TP979A 1005

TP979A 2005

DA Heating
DA Cooling

60-90

°

F

18 (124)

Adjustable

2-10

°

F

(1.1-5.6

°

C)

TP979B 1003

TP979B 2003

RA Heating
RA Cooling

TP979C 1001

TP979C 2001

DA Heating or

Cooling
RA Heating or
Cooling

TP979D 1009

TP979D 2009

DA Heating

DA Cooling

13 (90) Day

18 (124) Nite

Day/Nite Heat with
night set down; Cool
with night set up.

TP979E 1006

TP979E 2006

DA Heating
RA Cooling