Troubleshooting

(continued)

1 Not applicable on heating-only model.

Problem

Check

Action

Heat-on time too short.

— anticipator setting. (See Fig. 6 for

anticipator location.)

Increase anticipator setting by 0.05.
Observe heating system operation.

Heat-on time too long.

— anticipator setting. (See Fig. 6 for

anticipator location.)

Decrease anticipator setting by 0.05.
Observe heating system operation.

No cooling.

— system switch. May be in OFF or

HEAT position.

Move switch to COOL position.

— fuse or circuit breaker.

If fuse is blown or breaker tripped,
replace or reset.

— condenser switch position.

Located outdoors and may be
turned Off.

Move to ON position.

— Y, G, RC thermostat connections.

Turn Off power to cooling system. Check
for correct terminal hookups. Repair any
frayed or broken wires. Firmly tighten all
terminal screws.