Outdoor unit

5.Purging Method:

7

Push the air out of the indoor unit

and piping as followes:
(1) Remove the valve cap on 2-way

valve in outdoor unit.
(2) Loosen by 1/2 turn the flare nut of

gas pipe, which is conneted to

3-way valve.
(3) Loosen 2-way valve by 90

o

using

hexagon wrench, and after approx.

10 sec tighten it up. Gas comes out

through flare nut on wide pipe. If no

gas is discharged, tighten flare nut

with specified torque.

(4) Open 2-way and 3-way valves

using specified torque.

(5) Tighten the caps on the valves

with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

When connecting pipe exceeds 5 meters, 16g refrigerant shall be added

per exceeding meter. Charge according to the following list.

Piping length

Additional amount

5m

7m

No need

32g

During this procedure, 50g refrigerant will be discharged in piping.

(This must be strictly controlled within 90

o

and 10 sec.)

Brand new outdoor unit is charged 50g more refrigerant than regulated

weight. Only for first installation, this extra 50g can be used to purge air

in pipes.

Note: When extending piping, air inside piping shall be removed by using external

refrigerant gas, charge according to the following list.

10m

80g

3-way valve

2-way valve

6.35mm(1/4")

12.7mm(1/2")

HSU-18LEA13(T3)