Extension cords, Symbology – Harbor Freight Tools 92683 User Manual

Page 6

Advertising
background image

SKU 92683

For technical questions, please call 1-800-444-3353

Page 6

EXTENSION CORDS

1.

Grounded tools require a three wire extension cord. Double Insulated tools can use either a two or
three wire extension cord.

2. As the distance from the supply outlet increases, you must use a heavier gauge extension cord. Us-

ing extension cords with inadequately sized wire causes a serious drop in voltage, resulting in loss of
power and possible tool damage.

(See Figure C.)

3. The smaller the gauge number of the wire, the greater the capacity of the cord. For example, a 14

gauge cord can carry a higher current than a 16 gauge cord.

(See Figure C.)

4. When using more than one extension cord to make up the total length, make sure each cord con-

tains at least the minimum wire size required.

(See Figure C.)

5. If you are using one extension cord for more than one tool, add the nameplate

amperes and use the

sum to determine the required minimum cord size.

(See Figure C.)

6. If you are using an extension cord outdoors, make sure it is marked with the suffix “W-A” (“W” in

Canada) to indicate it is acceptable for outdoor use.

7. Make sure your extension cord is properly wired and in good electrical condition. Always replace a

damaged extension cord or have it repaired by a qualified electrician before using it.

8. Protect your extension cords from sharp objects, excessive heat, and damp or wet areas.

RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(120 OR 240 VOLT)

NAMEPLATE

AMPERES

(At Full Load)

EXTENSION CORD LENGTH

25 Feet

50 Feet

75 Feet

100 Feet 150 Feet

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

FIGURE C

* Based on limiting the line voltage drop to five volts at

150% of the rated amperes.

SYMBOLOGY

Double Insulated

Canadian Standards
Association

Underwriters Laboratories, Inc.

V~

Volts Alternating Current

A

Amperes

n0 xxxx/min.

No Load Revolutions per Minute
(RPM)

Advertising