Heat & Glo • EM-415/EM-415H • 31317 Rev Q • 10/06

20

E. Install the Attic Insulation Shield

An insulation shield must be installed when there is a pos-
sibility of insulation coming into contact with the factory built
chimney system.

• Bend the tabs at the top of the attic insulation shield inward.

This will help keep the chimney section centered in the
shield.

• Position the shield over the vertical chimney section where

it penetrates a ceiling fi restop.

• Slide the shield down until it rests on the ceiling fi restop.

The ceiling fi restop will support the insulation shield. See
Figures 5.6 and 5.7.

F. Double-check the Chimney Assembly

Continue assembling the chimney sections up through the
ceiling fi restops as needed. While doing so, be aware of the
height and unsupported chimney length limitations given un-
der Section 5.A. Chimney Requirements.

Check each section by pulling up slightly from the top to en-
sure proper engagement before installing the succeeding
sections. If they have been connected correctly, they will not
disengage when tested.

G. Secure the Chimney

When offsets and returns are joined to straight pipe sections,
they must be locked into position with the screws provided*
(outer only), using the predrilled holes. To prevent gravity
from pulling the chimney sections apart, the returns and the
chimney stabilizers have hanger straps for securing these
parts to joists or rafters. See Figure 5.8.

* or equivalent #6 or #8 sheet metal screw no longer than

3/4 in. (19 mm).

Attic

Insulation

Shield

Chimney

Insulation

Ceiling Firestop

Tabs

24 in.

(610 mm)

10-1/2 in.

(267 mm)

14-1/2 in. (368 mm)

Figure 5.6 Install Attic Insulation Shield Above the Ceiling

24 in.

(610 mm)

Attic

Insulation

Shield

Chimney

Insulation

10-1/2 in.

(267 mm)

14-1/2 in. (368 mm)

Ceiling Firestop

Tabs

Figure 5.7 Install Attic Insulation Shield Below the Ceiling

Ceiling

Firestop

Straps

Optional

Additional

Support

Joint

Band

(Optional)

Figure 5.8 Secure the Chimney

Fire Risk
• DO NOT pack insulation or other

combustibles: between ceiling fi restops;
between chimney and attic insulation
shield.

• ALWAYS maintain specifi ed clearances

around chimney and ceiling firestop
systems.

• Install

ceiling

fi restops as specifi ed.

Failure to keep insulation or other material
away from chimney pipe may cause fi re.

WARNING

Fire Risk
• Secure offsets with screws (not to exceed

3/4 in./19 mm in length).

WARNING

• Secure returns with strapping.
• Straight chimney sections may be secured with screws

(not to exceed 3/4 in./19 mm in length) at the joints.

Keep chimney sections from separating or twisting.