SUB SERIES INTERVAL DATA RECORDERS

9

62-0342—01

Fig. 13. Wiring overview for SUBIDR-16.

Note: Meter 1 must be installed within
100 feet of IDR. Meters 2-8 must be installed
within 500 feet of IDR.

(Up to 16 Meters)

(One of three channels shown for clarity.)

(Up to 16 Meters)

~

~

Channel 1 of 3

4-Conductor

Flat Modular Cable

Up to 4000 Feet Total

Daisy-Chain or

Star Connection

Up to 26 SUBIDR-16s per channel

(3 channels per SUB-RS232K)

AC Adapter

SUB-RS232K

6' cable provided by

Honeywell (15 ft max.)

8-conductor cable

& modular plug

DB-9 (DTE) Connector

PC

RJ-45

RJ-11

8-Cond.

RJ-45

RJ-11

6-Cond.

RJ-45

6-Cond.

RJ-45

Wiring Guide for SUBIDR-16

IDR A-B

IDR Y-Z

CONNECTION CABLE

TYPE CONNECTOR

SUBIDR to Honeywell Meter #1

8-cond. 22-26 AWG

RJ-45

flat

modular

cable

SUBIDR to Honeywell Meters #2-16

6-cond. 22-26 AWG

RJ-45

(Pins 1 & 8 not used)

SUBIDR to SUBIDR

4-cond. 26 AWG

RJ-11

IDR to RS-232 Key 2000

4-cond. 26 AWG

RJ-11

SUB-RS232K to Computer *

8-cond. 22-26 AWG

RJ-45/DTE

flat

modular

cable

SUB-RS232K to Modem *

8-cond. 22-26 AWG

RJ-45

flat

modular

cable

SUBIDR to SUB-USBK *

Allows connection directly

to

the

computer

USB

SUBIDR to Pulse Meter

2-cond. 14-22 AWG

* Supplied by Honeywell

Note: When constructing field-installed cables, modular cables must be made
so that the individual wires go through on the same pin number.

3rd

Party

Meter

3rd

Party

Meter

3rd

Party

Meter

Pair of wires

(#22-#14 AWG)