C. floor protection requirements – Harman Stove Company OAKLEAF 1-90-797000 User Manual

Page 12

Advertising
background image

12

Save These Instructions

Oakleaf Woodburning Stove

Dry Seasoned Wood Only!

3-90-798_R9

C. floor protection requirements

daNgER: The appliance legs may not be removed

for installation.

Minimum Size floor protection (USA) is 48" Deep By

32.5" Wide.

floor protection requirements

If the Oakleaf is being installed on a combustible floor,

the bottom heat shield (part # 1-00-797058) must be

installed along with proper floor protection material.

(See page 25). Floor protection must be a minimum

3/8" (9.5mm) thickness of material having an insulating

value equal to or better than 0.84k/in. (The lower the k

value, the better the protection.)

Another method for calculating floor protection is in

R value. This requirement would be for an R value of

0.45 or higher. (The higher the R value, the better the

protection). Example- 1 inch of Durock® = 0.52R

In all installations, the area under and around the stove

must be protected from falling ash and live coals. The

area under a horizontal run of chimney connector must

also be protected, extending two (2) inches beyond the

measurement of the horizontal connector.

Further guidelines for floor protection are as follows:

In the U.S. the floor protector must be completely

under the stove, and extending 16" in front of the door

opening, 8" to each side and 8" to the back.

In Canada, the floor protection must extend 18"

(457mm) in front of the door opening, 8" (203mm) to

each side and extend to the wall behind the stove.

L

j

floor protection

Requirements

Inches

Millimeters

Sides- USA /CANADA *

Rear- USA

8 203

8 203

L

Rear- CANADA

Wall Wall

k

Front- USA /CANADA *

16 457

* Floor protection for the front and sides as measured

from the appliance door opening.
Minimum 60" corner floor protection (CANADA).

j

j

k

L

Alternate floor protector dimension may be used as long

as they satisfy the measurement requirements shown

above.

Minimum size floor protection for a corner installation

hearth pad is 54" x 54" (USA ONLY).

54"

54"