2.0.

UPS Output Requirements

Note: The outputs of SG 5 & 6kVA models are not configured for 208 or 240Vac
split-phase operation. Please reference the output configuration diagrams on pages
9-10 prior to making any wiring connections to the UPS. Should a 208 or 240Vac
split-phase output configuration be required, please contact the factory.

MODEL

RECOMMENDED OUTPUT

CIRCUIT BREAKER

SG5K-1TX:

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

SG5K-2T

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: None

SG5K-2TX

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

SG6K-1TX

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

SG6K-2T

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: None

SG6K-2TX

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

IMPORTANT

OUTPUT REQUIREMENTS

8

View of the Input/Output Hardwire Terminal Block

This terminal block is located on the UPS rear panel and shown with the conduit mounting and

access cover plates removed.

Use only the lower terminals and wire securing screws when making wiring connections to

the UPS.

DO NOT USE THE UPPER TERMINAL CONNECTIONS

Refer to the Wire Gauge Table on Page 7 for recommended wire sizes.
Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified.
Refer to Pages 9-10 for the terminal wiring designations for your specific SG UPS model.

Terminal Designation Numbers

1 2 3 4 5 6 7 8 9 10