PIN ASSIGNMENT FOR THE FALCON

UA88373 OPTO-COUPLER OPTION BOARD

(no-bypass signal)

PIN

DESCRIPTION

1

Not Used

2

Utility Loss (N.O.) (Closes upon utility loss)

3

Utility Loss (N.C.) (Opens upon utility loss)

4

Common for pins 2, 3 & 5

5

Low Battery (N.O.) (Closes at low battery)

6

Remote Shutdown
Applying a +5-+12Vdc voltage level for >500ms,
while the UPS is on battery will shutdown the
UPS

7

Not Used

8

Not Used

9

Not Used

Typical Falcon Opto-coupler Interface Card

(A)

(E)

(K)

(B)

(C)

6

7

8

2

3

4

5

To CPU

Alarm Signal

DB-9

Low Battery Signal

Utility Loss

OPTO Board Internal Circuitry