Configuring the fieldserver as a ge-egd client, Client side connection parameters – FieldServer FS-8704-12 User Manual

Page 6

Advertising
background image

FS-8704-12 GE-EGD Driver Manual

Page 6 of 23

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5

CONFIGURING THE FIEL DSERVER AS A GE-EGD CLIENT

Historically, one uses the client-server model to describe the operation of most protocols. Recently producer-
consumer model protocols have started to become more numerous. The GE-EGD (Ethernet Global Data) is a
producer-consumer model protocol. In equating the two models it is important to regard the consumer as a
passive (FieldServer) client.
Other clients typically are active and poll for new data. The consumer is a passive
client in that waits to digest new data generated by a producer.

For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the FieldServer.
The information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a GE-EGD Producer.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for GE-EGD communications, the driver independent FieldServer buffers need to be declared in the
“Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and
the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on
how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1

Client S ide Connection Parameters

Section Title
Adapter
Column Title Function

Legal Values

Adapter

Adapter Name

N1,N2

1

Protocol

Specify protocol used ge_egd


Example

// Client Side Connections

Adapters

Adapter

, Protocol

N1

, ge_egd

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.