Map descriptor example, Example 1, Example 2 – FieldServer FS-8700-124 User Manual

Page 9: Example 1 4.5.2. example 2

Advertising
background image

ProtoNode Driver Manual (FS-8700-124) rev 6.doc Manual

Page 9 of 17


ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web:www.protocessor.com

Tel: 408.964.4433 Fax: 408.964.4425 Toll_Free: 800.317.8319 email: [email protected]

4.5.

Map Descriptor Example.

4.5.1.

Example 1

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Toshiba_Command,

Length,

Scan_Interval

A1,

DA_AI_01,

0,

RDBC,

Node_A,

OV1,

1,

5

4.5.2.

Example 2

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Toshiba_Command,

Length,

Scan_Interval

B1,

DA_DI_01,

23,

RDBC,

Node_A,

ALARM,

1,

5

B2,

DA_DI_01,

15,

RDBC,

Node_A,

ALARM,

4,

5

B3,

DA_DI_01,

0,

RDBC,

Node_A,

ALARM,

23,

5

For all commands except
FAULT and ALARM,
ensure that the
Data_Array_Name points
to an array of type float.

Make sure the Toshiba
command supports the
selected function.

For a list of
commands, see
Appendix A

All commands except
ALARM and FAULT
have length 1.

For ALARM and
FAULT, use bit
arrays

Use the offset to read a specific bit or
start reading at a specific bit. Use in
conjunction with length. Max value is
23.

Specify number of bits to
read. Maximum for Offset
+ Length is 23.