Ch10 h, Fficiency, Eries – Fedders CH1042CBD1VF User Manual

Page 2: Model specifications, Cooling performance data matched system

Advertising
background image

CH10

H

igh

E

fficiency

S

eries

MODEL SPECIFICATIONS

OUTDOOR

UNIT

MODEL*

EVAPORATOR

COIL

RATINGS AT STANDARD CONDITIONS

COOLING DATA AT EXTENDED OUTDOOR AMBIENTS °F.M.B.T.U.H.

BTUH

SEER

CFM

80

85

90

95

100

105

110

115

COOLING PERFORMANCE DATA MATCHED SYSTEM

CH1018BBD

E3009A

17 600

10

600

TOTAL

18 700

18 300

17 900

17 600

16 700

15 800

14 800

13 900

SENSIBLE

13 500

13 200

12 900

12 700

12 020

11 400

10 700

10 000

CH1024BBD

E3009A

22 600

10

800

TOTAL

24 500

23 900

23 200

22 600

21 400

20 200

19 000

17 900

SENSIBLE

17 600

17 200

16 700

16 300

15 400

14 500

13 700

12 900

CH1030BBD

E3612A

28 200

10

1000

TOTAL

29 800

29 300

28 700

28 200

26 600

25 000

23 500

21 900

SENSIBLE

21 500

21 100

20 700

20 300

19 100

18 000

16 900

15 800

CH1036BBD

E3618A

34 000

10

1250

TOTAL

37 300

36 400

35 500

34 600

31 900

28 800

25 900

23 000

SENSIBLE

26 900

28 400

25 600

24 900

23 000

20 700

18 600

16 600

CH1042CBD

E6016A

39 500

10

1350

TOTAL

42 400

41 800

41 100

39 500

38 900

37 300

35 800

34 200

SENSIBLE

30 600

30 100

29 600

28 400

28 000

26 900

25 800

24 600

CH1048CBD

E6026A

46 000

10

1700

TOTAL

49 700

48 500

47 300

46 000

44 400

43 000

41 500

39 800

SENSIBLE

35 800

34 900

34 000

33 100

32 000

31 000

29 900

28 600

CH1060CBD

E6037A

55 500

10

1850

TOTAL

59 200

57 900

56 700

55 500

54 000

52 600

51 100

49 700

SENSIBLE

42 600

41 700

40 800

40 000

38 900

37 900

36 800

35 800

*Basic model number only. See unit nomenclature on the last page for exact model number.

FOOTNOTES:

Amps at 104˚F OD temp. 80˚F DB / 67˚F WB indoor temp.

Time delay type fuse for HACR Circuit Breaker.

For indoor coils nomenclature see

indoor coil specification sheet.

Air handler includes evaporator coil.

MODEL NUMBER

CH1018BBD1VF

CH1024BBD1VF

CH1030BDD1VF

CH1036BBD1VF

CH1036BBD3VF

CH1036BBD4VF

PERFORMANCE DATA

NOMINAL COOLING BTU/H

17 600

22 600

28 200

34 000

NOMINAL HEATING BTU/H

17 600

22 000

27 000

34 400

SEER (COOLING) BTU/H-W

10.0

10.0

10.0

10.0

CFM

600

800

1000

1250

VOLTS/HZ/PHASE

208-230/60/1

208-230/60/1

208-230/60/1

208-230/60/1

208-230/60/3

460/60/3

VOLTAGE RANGE

197-253

197-253

197-253

197-253

187-253

415-508

OPERATING CURRENT AMPS

9.2

12.0

15.4

18.0

13.2

6.2

MIN. WIRE AMPACITY

11.3

14.7

18.0

22.4

16.5

15.0

MAX. HACR BREAKER

15

25

30

35

25

15

COMPRESSOR DATA

RLA

8.8

9.8

11.4

15.2

11.4

4.8

LRA

49

60

75

96

75

40

FAN DATA

DIAMETER

18 INCH / 3 BLADE

18 INCH / 3 BLADE

18 INCH / 3 BLADE

18 INCH / 4 BLADE

MOTOR TYPE

PSC

PSC

PSC

PSC

HP (W) / FLA

1/6 / 1.0

1/6 / 1.0

1/6 / 1.0

1/5 / 1.8

1/4 / 1.2

RPM

1075

1075

1075

1075

CFM

1800

1800

1800

2 400

OUTDOOR COIL

TYPE

ENHANCED ALUMINUM PLATE FIN / RIFLED COPPER TUBE

FACE AREA

9.8

9.8

9.8

12.0

O.D. / F.P.I.-ROWS

5/16 / 18-1

3/8 / 18-1

3/8 / 18-1

3/8 / 18-1

REFRIGERANT LINE CONNECTIONS (SERVICE VALVE PORT I.D.)

LIQUID

3/8 ID

3/8 ID

3/8 ID

3/8 ID

VAPOR

3/4 ID

3/4 ID

3/4 ID

3/4 ID

WEIGHTS

NET WEIGHT — lbs.

137

140

142

161

SHIPPING WEIGHT — lbs.

143

149

151

169