FieldServer Gamewell FS-8700-83 User Manual

Page 7

Advertising
background image

FS-8700-83 Gamewell

Page 5 of 24

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.3 Client Side Nodes

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric
characters

Node_ID

Gamewell panel node address.


The Node Id has no meaning
when the FieldServer is
connected directly to Gamewell
panel. When connecting to a
Gamewell panel directly always
set the Node_ID to zero. When
connecting to a Gamewell
SmartNet terminal. The
Node_ID is important and
should correspond to the
Node_ID’s of the panel’s
connected to the SmartNet
terminal.

0-256

Protocol

Specify protocol used

Gamewell

Port

Specify which port the device is
connected to the FieldServer.

The use of R1 and R2 is only
appropriate when a 232/485
converter is used. The
Gamewell panels only have a
232 port available for
connection.

P1-P8, R1-R2


Example

// Client Side Nodes

Nodes
Node_Name, Node_ID, Protocol, Port
Panel1 , 0 , Gamewell, P8

Advertising